S+S Regeltechnik AERASGARD RCO2-W Operating Instructions Manual Download Page 8

G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 
–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 
–  The CO2  sensor is shock-sensitive. Due to the mechanism’s design, the measuring result may vary if shaken. 
–  In case of pollution, we recommend cleaning and recalibration in the factory.
–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.
–  When several sensors are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage source 

may be short-circuited. 

–  The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.
–  If the automatic system (automatic balancing of CO2 measurand) is activated, a cyclical fresh air supply must be provided,  

as otherwise incorrect measurements can occur.  

–  The device must be permanently energized to measure the CO2 concentration correctly.
–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housings or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  

These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

Circuitry

Circuitry

Output

0V/GND

Output

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

Output

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
 supply  voltage. 

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it. 

Therefore, pay attention to correct wiring!

Summary of Contents for AERASGARD RCO2-W

Page 1: ...transducer self calibrating with multi range switching and active switching output F Notice d instruction Sonde d ambiance CO2 resp convertisseur de mesure auto calibrant avec commutation multi gamme...

Page 2: ...Ma zeichnung Geh use Baldur1 Dimensional drawing Housing Baldur1 Plan cot bo tier Baldur1 Baldur1 T K 6 0 85 85 27 2 Ma zeichnung Geh use Edelstahl Dimensional drawing Housing stainless steel Plan co...

Page 3: ...t Offset Potentiometer 10 vom Messbereich Relais Ausgang RCO2 SD ohne Wechsler RCO2 W mit potentialfreiem Wechsler 24 V 1 A Messgenauigkeit typisch 30 ppm 3 des Messwerts Temperaturabh ngigkeit 5 ppm...

Page 4: ...Kalibriervorganges ist f r ausreichend Frischluft zu sorgen CO2 Konzentration 350 500 ppm und darauf zu achten dass keine CO2 erzeugenden Vorg nge die Umgebungs luft beeinflussen Gehen Sie bei der man...

Page 5: ...atalogdarstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entf...

Page 6: ...tact RCO2 W with potential free changeover contact 24 V 1 A Measuring accuracy typically 30 ppm 3 of measured value Temperature dependence 5 ppm C or 0 5 of measured value C whichever is higher Pressu...

Page 7: ...ovided before and during the calibration procedure CO2 concentration 350 500 ppm Also make sure that no CO2 producing processes influence the ambient air Proceed as follows to perform manual calibrati...

Page 8: ...atalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warran...

Page 9: ...e la plage de mesure Sortie relais RCO2 SD sans inverseur RCO2 W avec inverseur libre de potentiel 24 V 1 A Pr cision de mesure typique 30 ppm 3 de la Vf D pendance en temp rature 5 ppm C ou 0 5 de la...

Page 10: ...talonnage automatique Assurer une alimentation en air frais suffisante avant et pendant le processus d talonnage teneur en CO2 350 500 ppm et veiller ce qu aucune op ration g n rant du CO2 n influence...

Page 11: ...la notice d instruction accompagnant l appareil sont applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s...

Page 12: ...5 C 0 13 2 15 0 50 C 1 2 0 14 1 5 ABS RAL 9010 V2A 1 4301 85 x 85 x 27 Baldur 1 100 x 100 x 25 55 III EN 60 730 IP 30 EN 60 529 CE EN 61326 2014 30 EU 2014 35 EU AERASGARD RFTM LQ CO2 1 AERASGARD RCO...

Page 13: ...OFF default ON DIP 4 0 10 default OFF 4 20 A ON 5x LED DIP 5 OFF ON DIP 2 RCO2 W A CO2 0 2000 1 0 5000 1 LED 1 LED 2 LED 3 LED 4 LED 5 350 350 20 416 536 40 482 722 60 548 908 80 614 1094 100 680 1280...

Page 14: ...0 10 24 CO2 CO2 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry Output 0V GND Output 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry Output 0V GND Power supply AC 24V 0V DC 15 36V GN...

Page 15: ...st knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devic...

Page 16: ...4 5 ON DIP zero set offset 12 11 13 NC NO COM Output CO2 in ppm UB 24V AC DC NC Normally Closed COM Common NO Normally Open UB GND Schaltbild RCO2 W Schaltbild RCO2 SD Connecting diagram RCO2 W Sch ma...

Reviews: