G
THERMASGARD
®
ATM2 - VA ID
Rev. ID20 - V12 (+U)
Calibratable outside temperature measuring transducer
THERMASGARD
®
ATM 2 - VA
with eight switchable measuring ranges, external sensor,
continuous output, housing made from stainless steel V4A, with cable gland or M12 connector according to DIN EN 61076-2-101. It is used to
detect outside temperatures, temperatures in wet rooms, e.g. for installation on outside walls, in cold storage buildings and greenhouses, in the
industrial sector and in agriculture. Installation in outdoor areas preferably at the north side of a building or in a protected place. In case of direct
solar irradiation, we recommend using our sun and ball-impact protection hood
WS 01
or
WS 03
(accessories). The sensor is factory-calibrated;
an environmental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
a
(Ohm) = (U
b
-14 V) ⁄ 0.02 A for I variant, see working resistance diagram
Load resistance:
R
L
> 5 kOhm for U variant
Power consumption:
< 1.0 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
Sensor:
Pt1000, DIN EN 60751, class B, (
Perfect Sensor Protection
)
Measuring ranges:
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Deviation, temperature:
typically ± 0.2 K at +25 °C
Ambient temperature:
measuring transducer –30...+70 °C
Output:
0 -10 V or 4...20 mA
Connection type:
2- or 3-wire connection
Electrical connection:
0.14 - 1.5 mm² via terminal screws
Cable connection:
cable gland, stainless steel V2A
(1.4305)
(M 20 x 1.5; with strain relief, exchangeable, inner diameter 6 - 12 mm)
or
M12 connector
(male, 5-pin, A-code) according to DIN EN 61076-2-101
Housing:
stainless steel V4A
(1.4571), with non-distortion cover bolting, impact resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant
Housing dimensions:
143 x 97 x 61 mm
(Tyr 2E)
Protective tube:
made from stainless steel
V4A
(1.4571), Ø 6 mm, nominal length NL = 65 mm
Process connection:
by screws
Protection class:
III (according to EN 60 730)
Protection type:
IP 65
(according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713160960B (Skadi2)
Standards:
CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
ACCESSORIES
see table
THERMASGARD
®
ATM 2 - VA
Outside temperature ⁄ wet room temperature measuring transducers,
ID
Type
Sensor
Output
Item No.
ATM 2 -x VA
with cable gland
AT M2-I VA
Pt1000
4... 20 mA
2001-6171-2200-001
AT M2-U VA
Pt1000
0 -10 V
2001-6171-1200-001
ATM 2 -x VAQ
with M12 connector
AT M2-I VAQ
Pt1000
4... 20 mA
2001-6171-2100-001
AT M2-U VAQ
Pt1000
0 -10 V
2001-6171-1100-001
Extra charge:
Other ranges optional
ACCESSORIES
WS-01
Sun and ball-impact protection hood,
184 x 180 x 80 mm, stainless steel
V2A
(1.4301)
7100-0040-2000-000
WS-03
Weather and sun protection hood
,
200 x 180 x 150 mm, stainless steel
V2A
(1.4301)
7100-0040-6000-000