Schematic diagram
Zero point calibration
The sensors are pre-set and calibrated at the factory.
Each measuring channel has a separate offset
potentiometer for subsequent adjustment of the
measurement. The adjusting range is ± 10 % of the
measuring range.
1 2 3 4
1 2 3 4
shield
shield
U
+
GND
A B
U
+
GND A B
mode
address
zero
offset
CO² CO²
VOC
VOC
r.H.
°C
1 2 3 4 5 6 7 8
ON
DIPA
1 2 3 4 5 6
ON
DIPB
DIP A: Bus address
DIP B: Bus parameters
(Baud rate, parity ...)
Telegram indicator
Reception (LED green)
Error (LED red)
Shielding
LED (internal status)
Offset correction
Sensor
VOC
Plug for
display
Sensor
CO
2
Reset button
1 2 3 4
1 2 3 4
shield
shield
U+
GND
A B
U+ GND A B
mode
address
zero
offset
CO² CO²
VOC
VOC
r.H.
°C
1 2 3 4 5 6 7 8
ON
DIPA
1 2 3 4 5 6
ON
DIPB
DIP A: Bus address
DIP B: Bus parameters
(Baud rate, parity ...)
Telegram indicator
Reception (LED green)
Error (LED red)
Shielding
LED (internal status)
Offset correction
Sensor
VOC
Plug for
display
Sensor
CO
2
Reset button
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC (± 10 %)
Power consumption:
< 4.4 W ⁄ 24 V DC typical; < 6.4 VA ⁄ 24 V AC typical;
peak current 200 mA
Data points:
temperature, relative humidity,
air quality (VOC), carbon dioxide (CO
2
)
HUMIDITY
Sensors:
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
Operating range, humidity:
0...95 % r. H. (non-precipitating air)
Deviation humidity:
± 3 % r.H.
(20…80 %) at +20 °C, otherwise ± 5 % r.H.
TEMPERATURE
Operating range, temperature: 0...+50 °C
Deviation, temperature:
± 0.2 K at +25 °C
AIR QUALITY (VOC)
VOC sensor:
VOC sensor (metal oxide)
with automatic calibration
VOC measuring range:
0...100 % air quality; with reference to calibration gas;
multi-range switching
VOC sensitivity low, medium, high
VOC measuring accuracy:
± 20 % final value (with reference to the calibration gas)
Service life:
> 60 months (under normal load conditions)
CARBON DIOXIDE (CO
2
)
CO
2
sensor:
optical NDIR sensor
with automatic and manual calibration
CO
2
measuring range:
0...5000 ppm
CO
2
measuring accuracy:
± 30 ppm ± 3 % of measured value
CO
2
temperature dependence: ± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C
(whichever is higher)
Pressure dependence:
± 0.13 % ⁄ mm Hg
Long-term stability:
< 2 % in 15 years
Gas exchange:
by diffusion
Bus parameters:
In the absence of current delivery
(under currentless conditions)
can be
configured and addressed via DIP switch!
Bus interface:
RS 485,
galvanically isolated,
bus termination can be
activated via DIP switch. Up to 32 devices possible
in one segment. In case of a greater number of devices,
RS 485 transceivers must be used.
Bus protocol:
Modbus (RTU-Mode), address range 0...
247
selectable
Baud rate:
9600, 19200, 38400 Baud
Status indicator:
Green LED = Telegram valid / red LED = Telegram error
Signal filtering:
4 s / 32 s
Ambient temperature:
0...50 °C
Warm up time:
approx. 1 hour
Response time:
< 2 minutes
Electrical connection:
0.2 - 1.5 mm
2
, via push-in terminal
Enclosure:
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions:
98 x 98 x 33 mm (Baldur 2)
Mounting:
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear
cable entry, with predetermined breaking point for
top/bottom cable entry for surface-mounted installation
Protection class:
III (according to EN 60 730)
Protection type:
IP 30 (according to EN 60 529)
Standards:
CE-conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
Optional:
two-line display with illumination,
cutout approx. 36 x 15 mm
(W x H), to display the actual humidity, actual temperature,
air quality and / or the actual CO
2
content
The maintenance-free microprocessor-controlled room sensor with Modbus connection with/without optional display, in elegant plastic housing, with snap-on
lid, base with 4-hole attachment
is an all-in-one device used for detecting all relevant measured values, such as humidity, temperature, CO
2
concentration
and air quality (VOC), thus enabling effective monitoring and control of the entire room climate. It measures CO
2
in the range from 0...5000 ppm, VOC in
one of three selectable sensitivity levels LOW / MEDIUM / HIGH, temperatures in the range from 0...+50°C as well as relative air humidity of 0...100 % r.H.
Relative humidity (% r.H.) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. A
digital, long-term stable sensor as a measuring element for relative humidity and temperature guarantees exact measurement results. The air quality is
determined based on a (VOC) mixed gas sensor. The CO
2
content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology).