S+S Regeltechnik 1202-7127-1421-000 Operating Instructions, Mounting & Installation Download Page 7

Switching   

output

  AHT - 30

Mode 1:

  Independent switchpoints for both relay outputs can be defined in the range of 5...95 %  r.H. by the control knobs (setpoint 1 for relay 1, 

setpoint 2 for relay 2, see schematic diagram). When the respective switchpoint is exceeded, the corresponding relay switches over (changeover 
contact  1 switches from position  2 to position  3). When the pre-set switchpoint is undershot again by more than 3 %  r.H. (hysteresis), the respective 
switching output switches back to the initial position (changeover contact 1 switches from position  3 to position  2). 

Mode 2:

  In Mode 2, only control knob setpoint 1 is active (setpoint 2 without function)! The switchpoint for the first relay is defined in the range of 

5...95 %  r.H. by the control knob setpoint  1 (see schematic diagram). The switchpoint for the second relay output is invariably defined in mode 2  
as "Switchpoint 1 + 5 %  r.H.". Hysteresis of 3 %  r.H. is also predefined for each switching output in mode  2. 

Mode 3:

  Independent switchpoints within the temperature range (selectable via DIP switches) for both relay outputs can be defined by the control knobs 

(setpoint 1 for relay 1, setpoint 2 for relay 2). If the respective switchpoint is exceeded, the corresponding relay switches over. If the pre-set threshold 
value is undershot again by 1 K (hysteresis), the respective switching output switches back to the initial position. The thresholds of the setting range 
(temperature) are 5 °C above the minimum or below the maximum range value respectively.

Mode 4:

  In mode 4, the control knob is allocated to setpoint 1 of the temperature, while control knob is allocated to setpoint 2 of the relative 

 humidity. The switchpoints can be set within the temperature range (selectable via DIP switches) or from 5...95 % r.H. (humidity). The thresholds  
of the setting range (temperature) are 5 °C above the minimum or below the maximum range value respectively.

Display readout

The 

1st line

 of the display shows the 

ACTUAL humidity

 in % r.H. and the  

ACTUAL temperature

 in °C. The displays showing the ACTUAL values alternate  

in a 3-second rhythm. The resolution is 1/10  % r.H. or 1/10 °C.
The 

3rd line

 shows information about the 

switching status of relay 1 and 2

  

(as circuits) on the left, and on the right for the 

switching values of relay 1 and 2

  

in % r.H. or °C (adjustable via the corresponding set potentio meter).  
The reference to respective measured value (relative humidity or  temperature)  
is determined by the mode selected.  
For improved legibility, backlighting is provided.

Zero point calibration

The sensors are pre-set and calibrated at the factory. Adjustment is possible either 
for temperature or relative humidity, depending on the output allocation (DIP switch 3).  
Range of adjustment: approx. ± 10 % r.H. or ± 5 K.

Supply

AC

DC

→   1

24 V∼

24 V  DC

→   4

0 V

GND

12

 

(A1) →

Relay 1

  Breaker contact

11

  (W1) →

Relay 1

  Changeover contact

13

 

(B1) →

Relay 1

  Normally open contact

22

 

(A2) →

Relay 2

  Breaker contact

21

  (W2) →

Relay 2

  Changeover contact

23

 

(B2) →

Relay 2

  Normally open contact

DIP switches 

AHT

 

- 30

Function mode

DIP 1 DIP 2

Mode 1

  (

2x 

  5...95 % r.H.)    (default)

OFF

OFF

Mode 2

  (5...95 % r.H. 

+  5 %

 r.H.)

O N

OFF

Mode 3

  (

2x 

  –35...+80 °C)

OFF

O N

Mode 4

  (5...95 % r.H.  /  –35...+80 °C)

O N

O N

Temperature range

DIP 3 DIP 4

–35...+35 °C

OFF

OFF

  0...+80 °C

O N

OFF

  0...+50 °C  (default)

OFF

O N

–35...+75 °C

O N

O N

Relay  2  switching  value

Relay 1 switching value

Relay  2 switching status  (

 ⁄ 

○)

Relay 1 switching status  (

 ⁄ 

○)

 

Circuit, empty 

 =   

relay in idle state

 

Circuit, full  

=   

relay energised

G  

Installation and Commissioning 

Rev.  2020 - V25

11

12 13

11

12 13

Gone below

preset

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Falls below 

the preset value with

3% r.H./1K hysteresis

Exceeding 

the preset value

Hysteresis

3% r.H./1K

Switching output 1

°C / % r.H.

21

22 23

21

22 23

Gone below

preset

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Falls below 

the preset value with

3% r.H./1K hysteresis

Exceeding 

the preset value

Hysteresis

3% r.H./1K

Switching output 2

°C / % r.H.

Summary of Contents for 1202-7127-1421-000

Page 1: ...Ausgang G Operating Instructions Mounting Installation On wall hygrostats and humidity and temperature sensors 2 0 electronic two step with multi range switching and continuous switching output F Noti...

Page 2: ...rfilter optional Metal sinter filter optional Filtre fritt en m tal en option AHT 30 35 50 126 90 112 20 4 M16x1 5 16 137 32 112 20 4 M16x1 5 16 134 M12 Steckverbinder optional auf Anfrage M12 connect...

Page 3: ...ung 35 85 C Betrieb 30 75 C nicht kondensierend Langzeitstabilit t 1 Jahr Geh use Kunststoff UV stailisiert Werkstoff Polyamid 30 glaskugelverst rkt mit Schnellverschlussschrauben Schlitz Kreuzschlitz...

Page 4: ...lbereiches Temperatur liegen jeweils um 5 C ber dem minimalen bzw unter dem maximalen Bereichswert 11 12 13 11 12 13 Schaltausgang 1 C r H eingestellte Schaltschwelle unterschritten eingestellte Schal...

Page 5: ...gef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Der Bet...

Page 6: ...75 C non precipitating Long term stability 1 per year Housing plastic UV stabilised material polyamide 30 glass globe reinforced with quick locking screws slotted Phillips head combination colour tra...

Page 7: ...ow the maximum range value respectively Display readout The 1st line of the display shows the ACTUAL humidity in r H and the ACTUAL temperature in C The displays showing the ACTUAL values alternate in...

Page 8: ...n are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeite...

Page 9: ...25 C sinon 3 0 cart temp rature typique 0 4 K 25 C Temp rature ambiante stockage 35 85 C fonctionnement 30 75 C sans condensation Stabilit long terme 1 an Bo tier plastique stabilis contre UV mati re...

Page 10: ...lage temp rature d passent respectivement la valeur de mesure minimale et maximale de 5 C 11 12 13 11 12 13 Gone below preset switchpoint threshold Preset switchpoint threshold exeeded Falls below the...

Page 11: ...eil sont applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos...

Page 12: ...6 126 x 90 x 50 Tyr 2 M 16 x 1 5 10 4 M12 DIN EN 61076 2 101 V2A 1 4301 16 55 III EN 60 730 IP 65 EN 60 529 0 14 1 5 2 CE 2014 30 EU 70 x 40 x 1 11 12 3 1 S1 11 12 2 21 22 3 1 S2 21 22 2 3 1 11 13 S1...

Page 13: ...80 C ON ON DIP 3 DIP 4 35 35 C OFF OFF 0 80 C ON OFF 0 50 C default OFF ON 35 75 C ON ON 2 1 2 1 r Rev 2020 V25 11 12 13 11 12 13 Gone below preset switchpoint threshold Preset switchpoint threshold...

Page 14: ...r ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry Output 0V GND Output 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry Output 0V GND Power supply AC 24V 0V DC 15 36V GND...

Page 15: ...heir particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our Gen...

Page 16: ...Common NO Normally Open Relais NC NO COM NC NO COM Passive sensor UB 24V AC DC UB GND Output humidity 4 20mA in r H Output temperature 4 20mA in C 1 2 5 6 3 4 12 11 13 22 21 23 1 setpoint 2 C offset...