 Load resistance diagram 

KFF - xx  ⁄  KFTF - xx 

4...20 mA

800

700

600

500

400

300
250

50

200

10

15

20

25

30 35 36 40

Load resistance diagram

W

orking r

esis

tanc

e  (Ohm)

Operating voltage  (V DC)

Admissible

  range

800

700

600

500

400

300
250

50

200

10

15

20

25

30 35 36 40

Load resistance diagram

W

orking r

esis

tanc

e  (Ohm)

Operating voltage  (V DC)

Admissible

  range

NOTE

For 4 ... 20 mA devices, DC voltage must be used  
(without residual  ripple, see permissible range of load 
resistance diagram). Do not use pulsating DC voltage.

Connecting diagram 

KFTF - xx - U 

Output: 

  

with  ⁄ without

 

0 -10 V

  

Display

Connecting diagram 

KFTF - xx - I  

Output: 

  

with  ⁄ without

 

4 ... 20  mA 

Display

NOTE

At transmitters with current output the humidity output (Pin 2)  
must categorically be connected !

1 2 3 4

230V AC

24V AC/DC

PLC

PC

+U

24

AC

/D

C

O

ut

pu

t h

um

id

ity 

in 

r.H

. 0

-1

0V

O

ut

pu

t t

em

pe

ra

tu

re 

in 

°C 

0-

10

V

–UB

-GN

D

1 2 3 4

230V AC

24V DC

+U

24

D

C

O

ut

pu

t h

um

id

ity 

in 

r.H

. 4

...

20m

A

O

utp

ut

 tem

per

at

ur

in

 °

C

 4

...

20m

A

PLC

Working

resistance

–UB  GND  (optional f

or

LCD back

gr

ound lightling)

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY VOLTAGE:

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output volt-
age is measured against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

HYGRASGARD

®

  KFF  ⁄  KFTF    (± 2,0 %),   KFF - 20  ⁄  KFTF - 20    (± 1,8 %)

Summary of Contents for 1201-3111-0000-029

Page 1: ...including mounting flange calibratable with multi range switching and active passive output F Notice d instruction Sonde d humidit et de temp rature 1 8 2 0 pour montage en gaine y compris bride de m...

Page 2: ...plastic Bride de montage en mati re plastique SF K Kunststoff Sinterfilter Standard plastic sinter filter standard Filtre fritt en mati re synth tique standard SF M Metall Sinterfilter optional Metal...

Page 3: ...KFF SD KFTF SD typisch 2 0 20 80 r H bei 25 C sonst 3 0 KFF 20 KFTF 20 typisch 1 8 10 90 r H bei 25 C sonst 2 0 Ausgang Feuchte 0 10 V bei U Variante 4 20 mA bei I Variante siehe B rdendiagramm TEMPER...

Page 4: ...Temperaturf hler 2 0 Standard Typ WG01 Messbereich Anzeige Feuchte Temperatur Ausgang Display Feuchte Temperatur Art Nr KFF IP65 aktiv KFF I 0 100 r H 4 20 mA 1201 3112 0000 029 KFF I DISPLAY 0 100 r...

Page 5: ...000 030 KFF 20 U T YR 2 DISPLAY 0 100 r H 0 10 V 1201 8111 0400 030 KFTF 20 IP65 aktiv KFTF 20 I 0 100 r H 35 75 C 35 35 C 0 50 C 0 80 C 4 20 mA 4 20 mA 1201 3112 1000 030 KFTF 20 I T YR 2 DISPLAY 0 1...

Page 6: ...eratursensor 1 2 3 4 5 6 passives Element UB GND Ausgang Temperatur 0 10V in C Ausgang Feuchte 0 10V in r H UB 24V AC DC z B Pt1000 Ni1000 LMZ235Z 4 oder 6 Leiter KFTF I Anschluss passiver Temperaturs...

Page 7: ...5 35 C C UA in V IA in mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4 3 10 9 0 5 0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 Te...

Page 8: ...dieser Ger tevariante eine Einweggleichrichtung bzw Verpolungschutzdiode integriert Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC Versorgungs spannung bei 0 10 V Ger ten Das Ausga...

Page 9: ...f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat...

Page 10: ...otherwise 3 0 KFF 20 KFTF 20 typically 1 8 10 90 r H at 25 C otherwise 2 0 Output humidity 0 10 V for U variant 4 20 mA for I variant see load resistance diagram TEMPERATURE Measuring range multi ran...

Page 11: ...ure sensors 2 0 Standard Type WG01 Measuring Range Readout Humidity Temperature Output Display Humidity Temperature Item No KFF IP65 active KFF I 0 100 r H 4 20 mA 1201 3112 0000 029 KFF I DISPLAY 0 1...

Page 12: ...3112 0000 030 KFF 20 I T YR 2 DISPLAY 0 100 r H 4 20 mA 1201 8112 0400 030 KFF 20 U 0 100 r H 0 10 V 1201 3111 0000 030 KFF 20 U T YR 2 DISPLAY 0 100 r H 0 10 V 1201 8111 0400 030 KFTF 20 IP65 active...

Page 13: ...connection passive temperature sensor 4 wire KFTF xx U connection 3 or 4 wire KFTF xx I connection Transmitter 2 or 3 wire KFF xx I connection Transmitter 3 wire KFF SD U connection 1 2 3 4 UB GND Fre...

Page 14: ...C UA in V IA in mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4 3 10 9 0 5 0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 Temperatu...

Page 15: ...polarity protection a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on AC supply volt...

Page 16: ...d This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the local energy supply company must be obser...

Page 17: ...95 h r sans condensation de l air cart humidit KFF KFTF KFF SD KFTF SD typique 2 0 20 80 h r 25 C sinon 3 0 KFF 20 KFTF 20 typique 1 8 10 90 h r 25 C sinon 2 0 Sortie humidit 0 10 V pour variante U 4...

Page 18: ...midit et de temp rature 2 0 Standard Type WG01 plage de mesure affichage humidit temp rature sortie cran humidit temp rature r f rence KFF IP65 actif KFF I 0 100 h r 4 20 mA 1201 3112 0000 029 KFF I D...

Page 19: ...0 030 KFF 20 I T YR 2 DISPLAY 0 100 h r 4 20 mA 1201 8112 0400 030 KFF 20 U 0 100 h r 0 10 V 1201 3111 0000 030 KFF 20 U T YR 2 DISPLAY 0 100 h r 0 10 V 1201 8111 0400 030 KFTF 20 IP65 actif KFTF 20 I...

Page 20: ...ure 4 20 mA in C UB GND optional for LCD background lighting Plug display Passive sensor DIP switches multi range switching Offset Temperature 5 K Humidity 10 r H 1 2 3 4 UB GND Free Output humidity i...

Page 21: ...lage de mesure 35 35 C C UA en V IA en mA 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4 3 10 9 0 5 0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9...

Page 22: ...polarit c d elle comprend un redressement demi onde diode de re dressement Gr ce cette diode de redressement int gr e les appareils 0 10 V peuvent galement tre aliment s en courant alternatif Le signa...

Page 23: ...ce les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L nders de leurs organes de surve...

Page 24: ...0 0 10 B U 4 20 I 35 35 C 35 75 C 0 50 C 0 80 C 0 10 B 4 20 35 85 C 30 75 C 0 2 K 25 C 0 10 B 4 20 0 14 1 5 30 RAL 9016 KFF xx KFTF xx 72 x 64 x 37 8 Tyr 1 01 KFF KFTF c 72 x 64 x 43 3 Tyr 1 KFF 20 KF...

Page 25: ...DIN EN 61076 2 101 HYGRASGARD KFF 2 0 Standard HYGRASGARD KFTF 2 0 Standard WG01 KFF IP65 KFF I 0 100 4 20 A 1201 3112 0000 029 KFF I DISPLAY 0 100 4 20 A 1201 3112 0200 029 KFF U 0 100 0 10 1201 3111...

Page 26: ...0 4 20 A 1201 8112 0400 030 KFF 20 U 0 100 0 10 1201 3111 0000 030 KFF 20 U T YR 2 DISPLAY 0 100 0 10 1201 8111 0400 030 KFTF 20 IP65 KFTF 20 I 0 100 35 75 C 35 35 C 0 50 C 0 80 C 4 20 A 4 20 A 1201 3...

Page 27: ...Passive element UB GND Output temperature in C 0 10V Output humidity in r H 0 10V UB 24V AC DC e g Pt1000 Ni1000 LMZ235Z 1 2 3 4 5 6 Passive element UB GND optional for backlighting Output temperature...

Page 28: ...5 19 2 75 10 0 20 0 35 35 C C UA B IA A 35 0 0 4 0 30 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4 3 10 9 0 5 0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9...

Page 29: ...TF xx U 0 10 KFTF xx I 4 20 A 2 1 2 3 4 230V AC 24VAC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temperature in C 0 10V UB GND 1 2 3 4 230V AC 24V DC UB 24V DC Output humidity in r H 4...

Page 30: ...30 r 0 100 0 10 4 20 10 0 99 9 0 10 24 ZVEI VDE EMV...

Page 31: ...stics Since the devices are used under a wide range of different conditions and loads beyond our control their particular suitability must be verified by each customer and or end user themselves Exist...

Page 32: ...90 50 20 112 20 4 32 3 13 4 35 112 90 32 3 32 M16x1 5 M16x1 5 SF M Tyr1 Tyr2 Metall Sinterfilter optional Schutzrohr aus Edelstahl optional auf Anfrage Metal sinter filter optional Protective tube sta...

Reviews: