Micro SD card page showing the SD card status, data consumption and last format date.
Display
Ethernet page showing the Site ID, the Ethernet S/W version, revision number and the
communication state.
Display
The UP and Down push buttons are used to scroll between the above pages. To access the parameters
menu, Press and release the Select push button.
2.1.2 SYMBOLS DESCRIPTIONS
Symbol
Description
Generator is off.
When blinking, it indicates that the generator is requested to start/stop or it is
running with an anomaly or/and no valid OK feedback.
When On, it indicates that the generator supply is within the acceptable limits,
the phases are all present and in the right sequence, and the OK signal is
active.
Mains power source is absent.
When blinking, it indicates that the Mains power source is detected but with
no valid measurements or/and wrong phase sequence.
When On, it indicates that the Mains supply is within the acceptable limits, the
phases are all present and in the right sequence.
Generator is in a faulty status with no start order, Fault reset is needed.
Generator Failed to start and the start order is active (hold start is enabled).
Order to disengage contactor is given.
Order to engage contactor is given.
The exclamation mark blinks to indicate that Order to disengage contactor is
given but the contactor feedback is active.
The exclamation mark blinks to indicate that Order to engage contactor is
given but the contactor feedback is inactive.
2. FRONT
PANEL
DESCRIPTION
Summary of Contents for OMEGA-ATS