Name
type
Address
Size
Access Description
G1 Exercising status
input register
30014
1
R
0 = Not Exercising
1 = Exercising Needed
2 = Exercising requested
3 = Exercising stopped
G2 Exercising status
input register
30015
1
R
0 = Not Exercising
1 = Exercising Needed
2 = Exercising requested
3 = Exercising stopped
Utility RN voltage
input register
30016
1
R
Utility phase R-Neutral voltage in V
Utility SN voltage
input register
30017
1
R
Utility phase S-Neutral voltage in V
Utility TN voltage
input register
30018
1
R
Utility phase T-Neutral voltage in V
Utility RS voltage
input register
30019
1
R
Utility phase R to phase S voltage in V
Utility ST voltage
input register
30020
1
R
Utility phase S to phase T voltage in V
Utility TR voltage
input register
30021
1
R
Utility phase T to phase R voltage in V
G1 RN voltage
input register
30022
1
R
G1 phase R - Neutral voltage in V
G1 SN voltage
input register
30023
1
R
G1 phase S - Neutral voltage in V
G1 TN voltage
input register
30024
1
R
G1 phase T - Neutral voltage in V
G1 RS voltage
input register
30025
1
R
G1 phase R to phase S voltage in V
G1 ST voltage
input register
30026
1
R
G1 phase S to phase T voltage in V
G1 TR voltage
input register
30027
1
R
G1 phase T to phase R voltage in V
G2 RN voltage
input register
30028
1
R
G2 phase R - Neutral voltage in V
G2 SN voltage
input register
30029
1
R
G2 phase S - Neutral voltage in V
G2 TN voltage
input register
30030
1
R
G2 phase T - Neutral voltage in V
G2 RS voltage
input register
30031
1
R
G2 phase R to phase S voltage in V
G2 ST voltage
input register
30032
1
R
G2 phase S to phase T voltage in V
G2 TR voltage
input register
30033
1
R
G2 phase T to phase R voltage in V
Utility frequency
input register
30034
1
R
Utility frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
G1 frequency
input register
30035
1
R
G1 frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
G2 frequency
input register
30036
1
R
G2 frequency in Hz *10 format (i.e. if this register
value is 504 this means that the frequency is 50.4Hz)
RN current
input register
30037
1
R
Line R current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
SN current
input register
30038
1
R
Line S current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
TN current
input register
30039
1
R
Line T current in A *10 format (i.e. if this register
value is 125 this means that the current is 12.5A)
Power (KW)
input register
30040
1
R
Power in KW
Digital Inputs
input register
30041
1
R
Omega Digital Inputs
Each bit represents an input (first input is the LSB)
Bit0: IP1
Bit1: IP2
...
Bit6: IP7
Digital Outputs
input register
30042
1
R
Omega Digital Outputs
Each bit represents an output (first output is the LSB)
Bit0: OP1
Bit1: OP2
...
Bit7: OP8
Operating Mode
holding
register
40001
1
R/W
Operating Mode:
1 = Auto Mode
2 = Mains-Only Mode
3 = G1-Only Mode
4 = G2-Only Mode
G1 Hourmeter
holding
register
40002
2
R/W
G1 Hourmeter
G2 Hourmeter
holding
register
40004
2
R/W
G2 Hourmeter
Summary of Contents for OMEGA-ATS
Page 2: ......
Page 35: ...6 DIMENSIONS 6 DIMENSIONS...
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ...0 1 2 3 4 5 0 1 2 3 4 5 0 1 0 1 2...
Page 41: ...6 6 6 6 6 6 6 6 6 6 6 6...
Page 45: ......
Page 46: ......