4. Connect the Current Probes
Please note that connecting the current probes is
a.
a crucial part of the data gathering process. Please
make sure you connect them to ensure that all
supporting data is gathered.
Connect the current probes around L1, L2, L3, N
b.
& G (or all applicable phases) and make sure that
there is only one phase in each current probe.
Make sure that each current probe is encompass-
c.
ing the correct phase and that the direction of the
arrow on the probe is pointing toward the load.
Plug the connector end of the current probes
d.
into their corresponding ports on the front of the
Power Monitor (to the right of the color-coded
voltage ports).
Caution: If running the CT wires out
of the panel or system, wrap the “Safe-
ty Sleeves” provided in the safety kit
around wires at pinch points.
Hard wired connection
EQUIPMENT
Current flow direction