GENERAL FUNCTION
Please read these instructions carefully and ensure that the mixing valve is
installed to Local Authority Regulations.
The Planar™ 230 and 330 thermostatic mixing valves are suitable for use
on low pressure hot and cold water supplies down to a minimum of 0.2
bar dynamic pressure (2 metre head) when used with the appropriate low
pressure shower heads. For best performance the recommended dynamic
pressure range is 0.5 - 2.0 bar (5 metre- 20 metre head) with a pressure
loss ratio of no more than 2:1. The thermostatic shower is factory preset
to 41°C ± 3°C with a balanced flow pressure of 2 bar. If the maximum tem-
perature setting is affected due to special installation conditions, the ther-
mostat can be adjusted on site to compensate.
WORKING PARAMETERS AND SPECIFICATIONS
Planar™230
Planar™330
Minimum flow pressure:
0.2 bar
0.2 bar
Test pressure static:
16.0 bar
16.0 bar
Working pressure dynamic:
3.5 bar max.
3.5 bar max.
Maximum pressure loss ratio: 2:1
2:1
Maximum hot water
temperature at the inlet:
85°C
85°C
Recommended stored
temperature:
60°C
60°C
Minimum hot/blend
temperature difference to
ensure shut-off on cold
supply failure:
15°C
15°C
Factory setting at 2 bar
equal pressures:
41°C ± 3°C
41°C ± 3°C
Minimum flow rate
8 LPM
10 LPM
Flow delivery at 40°C mixed
water temperature at 1
bar pressure loss:
75 LPM
110 LPM
At flow pressures of over 3.5 bar, or when the differential is >2:1, it is
recommended that a Syr pressure reducing valve be fitted in the supply
line(s).