RVP 6536 SERIES Service Manual Download Page 7

7

operation of both 1

st

 and 2

nd

 stage units.  However, if when

powering both systems from the on-board generator and the
cooling demand does not require that both systems operate,
stage two will shut down leaving stage one in operation. 

Heat operation always energizes both stages, 

however, only

stage one operates if power is not available to circuit #2.

B.

Thermostat

This thermostat is designed to operate 12 VDC controlled
heating and air conditioning systems.  It can control one stage
of heating and two stages of cooling.  It is a manual
changeover type of thermostat between heating and cooling. 
Manual changeover indicates that the operator must manually
switch the thermostat from cooling operation to heating.  The
thermostat will not make this change automatically.  It also
incorporates time delay circuitry.  The user selectable heating
mode on the sub-base allows gas heat control or heat pump
operation.

The time delays amount to 3 minutes between off and on
cycles.  Thirty seconds of this time delay is at the turn on of
the compressors.  This is to allow time for generators to
stabilize when initially starting.  The balance of the delay (2.5
minutes) occurs when the compressors cycle off.  This is to
allow time for the air conditioner pressures to balance before
restarting.  This delay will eliminate problems associated with
short cycling and will extend equipment life.  There is thirty
seconds and two degrees between 1

st

 and 2

nd

 stage cooling. 

The thermostat will not call for 2

nd

 stage cooling until room

temperature rises 2 degrees above the 1

st

 stage starting

temperature.  Once the thermostat calls for 2

nd

 stage cooling,

a 30 second delay is incurred to prevent both stages from
starting together.

The operating setpoints are changeable to suit the comfort
needs of the occupants.  Instructions for setting operating
temperatures (the setpoints) are covered in “Adjusting
Setpoint”.

7.  THERMOSTAT CONTROL PANEL

A.  OPERATION

Your air conditioner is operated from the control panel
located on the electronic wall mounted thermostat.  When the
furnace is connected to this thermostat, it will be operated
from the same control panel.

Identification and operational descriptions for all control
panel switches and display are listed below:

1.

Liquid Crystal Display - We will start with the
display because the display will be visible any time
the system is in operation.  The display will remain
visible while the thermostat is on and powered.

2.

System Switch - The system switch has four
positions to control the operation of the heating and
air conditioning systems.  They are as follows:

COOL - When in the cool position, 1

st

 and 2

nd

 stage

cooling will cycle from the cooling system setpoint.
Blower operation will be controlled by the position
of the Cooling Fan Switch.

HEAT - When in the heat position, the heating 
system will cycle from the heating system setpoint.
Heat will be by electricity (heat pump) or gas as
selected on sub-base.  The gas heating blower will 
operate per the heating system manufacturer
specifications.

OFF - When in the off position, no thermostat or
system operation will occur.

FAN - When in the fan position, the 

cooling blower

will operate continuously at high speed.

Summary of Contents for 6536 SERIES

Page 1: ...SERVICE MANUAL FOR 6536 SERIES PACKAGED HEAT PUMPS...

Page 2: ...d by some states to be licensed PERSONS NOT QUALIFIED SHALL NOT INSTALL NOR SERVICE THIS EQUIPMENT NOTE The words Shall or Must indicate a requirement which is essential to satisfactory and safe produ...

Page 3: ...UNIT DIMENSIONS AND SPECIFICATIONS PACKAGE AIR CONDITIONER MODEL NUMBER BREAKDOWN FOLLOWS 6 5 3 6 8 9 1 Model Series Revision Letter 6 Panasonic Compressor s 7 Sanyo Compressor s 8 Tecumseh Compresso...

Page 4: ...4 4 UNIT SPECIFICATIONS AND IDENTIFICATION...

Page 5: ...E 1 Indoor Condensate Drain Do Not Block Outdoor Air Exit Do Not Block View From Bottom Of Pan FIGURE 2 Provide Support In Cross Hatched Areas Shown Compressor Cabinet Door FIGURE 3 5 UNIT DEPICTION F...

Page 6: ...ate drainage off the roof to below the floor of the vehicle The heat pump contains a dual compressor system It combines the capacity of two roof mounted units into one highly efficient and compact pac...

Page 7: ...tage cooling until room temperature rises 2 degrees above the 1st stage starting temperature Once the thermostat calls for 2nd stage cooling a 30 second delay is incurred to prevent both stages from s...

Page 8: ...s room temperature The cooling system fan operates continuously at high speed No other components or systems are operating HEATING Move the system switch to HEAT The display will indicate room tempera...

Page 9: ...8 PACKAGED AIR CONDITIONER BLOWER PERFORMANCE DATA TEST CONDITION 115 VAC 60 HZ 1 PHASE DRY COIL CHART 1 9 INDOOR BLOWER MOTOR REMOVAL 1 Remove indoor blower access panel 2 Disconnect wiring from moto...

Page 10: ...roll in orientation shown Section 2 Torque nut to 65 in lbs min Section 3 Ground wire terminal assemblies between screw head and washer Section 4 Motor rotation wires to be connected Yellow to Yellow...

Page 11: ...ect wiring from motor terminal block 3 Remove scroll motor assembly from the unit 4 If at this point only the blower wheel needs replaced then remove 4 screws from inboard venturi Remove and replace b...

Page 12: ...FIGURE 9 BOTTOM VIEW 1 Wheel must be mounted with a minimum of 1 4 clearance to both venturis 2 Apply grease to motor shaft before assembling wheel 3 Torque set screw on flat of shaft to 110 10 in lb...

Page 13: ...Bracket SIDE VIEWS 1 Position motor with terminal block opposite motor mount clamp 2 Torque nut to 65 in lbs min 3 Ground wire terminal assembles between screw head and washer Wrap wire around motor...

Page 14: ...Remove clamps holding restrictor in place See 17 Figure 12 6 Unbraze by flow restrictor from points 16 Make note of plumbing locations for new restrictor Must be installed in same manner Note to prot...

Page 15: ...5 Unbraze refrigerant from points See 1 and 5 Figure 12 Protect wiring and insulation from torch flame 6 Remove screws See 7 8 9 Figure 12 Evaporator coil can now be removed Note Upon reassembly the r...

Page 16: ...e from system systems being serviced 4 Remove terminal caps See 13 Figure 12 5 Remove wiring from compressor terminal block cut wire ties on suction line 6 Remove reversing valve clamp from compressor...

Page 17: ...hermostat Assembly 12 VDC Thermostat plug positions on the p c board If no voltage is detected at the p c board connector check for voltage at the thermostat Note All functions of this heat pump are s...

Page 18: ...18 17 WIRING DIAGRAM 6536 Series Packaged Heat Pump 2 Compressor...

Page 19: ...19 18 WIREBOX COMPONENT CHECKOUT...

Page 20: ...perature Undersized Refrigeration System Very Little Or No Refrigerant Charge Compressor Thermostat Wiring P C Board Reversing Valve HEATING MODE Problems 1 Nothing Runs Heat Mode 2 IDFM Runs No Compr...

Page 21: ...B Serious thermostat or p c board damage may occur To use these flow charts start at the top left corner Using a volt ohm meter check what is indicated in that box If the answer to what is indicated i...

Page 22: ...Refer to Indoor High Checkout Cool Mode High Low Comp 2 Refer to 2 Operation Cool Mode O D Blower High O D Blower High L E D Comp 1 O D Blower Low L E D O D Blower Low Refer to Outdoor Blower High NO...

Page 23: ...Board See Figure 14 N O N O L I G H T If Green L E D Will Still Not Remain On After Coil Temperature Is OK Check Thermister For Continuity Caution It May Have A Very High Resistance Replace Thermiste...

Page 24: ...Check All Pin Connectors And Connections From Thermostat Replace Lifeline If Necessary O K NO 115 VAC To N O Contact Relay 3 And T5 On P C Board See Figure 13 O K NO Replace P C Board Check Wiring To...

Page 25: ...And Connection From Thermostat Replace Lifeline If Necessary 115 VAC To N O Contact On Relay 4 And T5 On P C Board See Figure 13 NO O K NO NO O K NO O K O K NO Replace P C Board O K Check Wiring To Mo...

Page 26: ...f Relay If Welded Check Compressor 1 Relay Operation NO O K Reconnect Wires Or Replace Components As Necessary Check Compressor 1 Start Device Check For Proper Wiring To Compressor Check Compressor Ru...

Page 27: ...All Pin Terminals And Connections From Thermostat Replace Lifeline If Necessary NO O K O K Check Compressor 2 Relay Operation Replace Relay If 12 VDC Is Present And Relay Won t Close Or If Relay Is W...

Page 28: ...28 CHECKOUT OUTDOOR BLOWER LOW SPEED HEATING AND COOLING MODES...

Page 29: ...L1 Line Power From Compressor 2 Relay Refer To Compressor 2 Checkout NO O K 115 VAC To T12 T13 On P C Board Replace P C Board NO O K Check Wiring To O D Blower Check Capacitor Check Motor For Open Or...

Page 30: ...N O Compressor 1 N O Refer To O D Blower Low Checkout Refer To Reversing Valve Checkout Refer To Compressor 1 Checkout Heat Mode 30 Second Delay On Make And Compressor 2 Is Energized O D Blower Low S...

Page 31: ...ll Not Remain On After Coil Temperature Is OK Check Thermister For Continuity Caution It May Have A Very High Resistance Replace Thermister If Open Check 12 VDC To Pin Connectors R B On P C Board See...

Page 32: ...onnectors And Connectors From Thermostat Replace Lifeline If Necessary NO NO NO O K 115 VAC To N O Contact On Relay 4 And T5 On P C Board See Figure 14 NO Replace P C Board O K Check Wiring To Motor C...

Page 33: ...Unit N O Check For 12 VDC Between W White B Blue Wires On The Thermostat YES Replace Sub base N O Check For 12 VDC Between R Red B Blue Wires On the Thermostat Y E S N O Restore 12 VDC To The Thermos...

Page 34: ...34 HEAT PUMP COMPRESSOR 2 CHECKOUT HEAT MODE Note All Operating Functions Subject To Thermostat And P C Board Time Delays Sub base Must Be In Electric Mode...

Page 35: ...stat And P C Board Time Delays Note If Compressor And Fan Motors Not Running Refer To Proper Checkouts Once The Reversing Valve Has Energized The P C Board Locks The Valve Into An Energized Position U...

Page 36: ...RV Products A Division of Airxcel Inc P O Box 4020 Wichita KS 67204 1976A281 1 00 PP...

Reviews: