background image

46

BLOWER SPEED SELECTIONS

The UT Electronic Controls control boards have four quick con-
nect terminals for connecting the motor speed leads. These are:

 1.   FAN SPEED* — motor runs on this speed when the thermo-

stat is in the “FAN” position.

 2.   COOL — connect desired cooling speed.

 3.   HEAT — connect desired heating speed.

 4.   HEAT/COOL* — connect desired speed when heating and

cooling speed are the same.

 5.   If heating and continuous speed are the same, jump across

“FAN” and “HEAT” terminals.

See Table 10 for instructions for setting the blower “OFF” timings.

GAS FURNACE (DIRECT DRIVE) 
INSTRUCTIONS FOR CHANGING
BLOWER SPEED

The blower motor is wired for blower speeds required for normal
operation as shown.

If additional blower speed taps are available (leads connected to
“M1” and “M2” on the electronic control), speeds may be changed
if necessary to fit requirements of the particular installation. Re-
connect the unused motor leads to “M1” or “M2.” Check motor
lead color for speed designation.

Heating speeds should not be reduced where it could cause the
furnace air temperature to rise to exceed the maximum outlet air
temperature specified for the unit.

!

CAUTION

DO NOT CONNECT ANY MOTOR SPEEDS TO “HEAT” OR
“COOL” IF YOU USE THE “HEAT/COOL” TERMINAL. DOING
SO WILL DAMAGE THE BLOWER MOTOR. UNUSED
MOTOR WIRE TAPS MUST BE CONNECTED TO PARKING
TERMINALS M1 AND M2 OF THE IFC, OR PROPERLY IN-
SULATED.

!

WARNING

DISCONNECT THE ELECTRICAL SUPPLY TO THE FUR-
NACE BEFORE ATTEMPTING TO CHANGE THE BLOWER
SPEED. FAILURE TO DO SO CAN CAUSE ELECTRICAL
SHOCK RESULTING IN SEVERE PERSONAL INJURY OR
DEATH.

        Low                   823                    803                   787                   732                   718                    691                    651                  593

     Med. Lo               1030                  1018                 1006                  976                   929                    897                    850                  808

     Med. Hi               1129                  1132                 1112                 1087                 1054                  1028                   971                  919

        High                  1361                  1353                 1331                 1297                 1264                  1232                  1164                1117

        Low                  1229                  1200                 1181                 1155                 1120                  1078                  1013                 970

     Med. Lo               1308                  1267                 1266                 1233                 1204                  1176                  1113                1062

     Med. Hi               1553                  1542                 1516                 1491                 1451                  1417                  1358                1306

        High                  1969                  1924                 1893                 1840                 1803                  1728                  1657                1570

        Low                  1209                  1182                 1131                 1112                 1051                   976                    929                  867

     Med. Lo               1438                  1420                 1386                 1350                 1320                  1293                  1248                1186

     Med. Hi               1902                  1883                 1844                 1817                 1753                  1700                  1636                1547

        High                  2071                  2037                 2001                 1962                 1905                  1856                  1807                1709

        Low                  1358                  1354                 1331                13091                1250                  1224                  1154                1089

     Med. Lo               1541                  1517                 1476                 1453                 1416                  1371                  1339                1277

     Med. Hi               1799                  1774                 1746                 1712                 1691                  1629                  1554                1495

        High                  2015                  1989                 1929                 1902                 1862                  1815                  1742                1665

        Low                  1411                  1395                 1370                 1334                 1310                  1252                  1220                1150

     Med. Lo               1606                  1579                 1569                 1537                 1499                  1468                  1407                1346

     Med. Hi               1889                  1891                 1849                 1828                 1764                  1717                  1659                1609

        High                  2178                  2160                 2105                 2067                 2024                  1976                  1916                1832

TABLE 12

AIR FLOW PERFORMANCE – (-)801S/(-)801P & (-)(-)80MSS/(-)(-)80MSP SERIES MODELS

Model

Motor HP

Blower Size,

IN.

CFM Air Delivery

External Static Pressure, ” W.C.

Speed Tap

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

(-)801SA050314MSA
(-)801PA050314MSA
(-)(-)80MSS050A30A
(-)(-)80MSP050A30A

1/3

11 x 6

(-)801SA075417MSA
(-)801PA075417MSA
(-)(-)80MSS075B30A
(-)(-)80MSP075B30A

(-)801SA100521MSA
(-)801PA100521MSA
(-)(-)80MSS100C40A
(-)(-)80MSP100C40A

(-)801SA125524MSA
(-)801PA125524MSA
(-)(-)80MSS125D50A
(-)(-)80MSP125D50A

1/2

11 x 7

1/2

11 x 10

3/4

11 x 10

(-)801SA150524MSA
(-)801SA150524MSA
(-)(-)80MSS150D50A
(-)(-)80MSP150D50A

3/4

11 x 10

NOTE: Shaded data is factory heating tap.

Ai

rfl

ow

Summary of Contents for 801P SERIES

Page 1: ...D 801P UPFLOW HORIZONTAL SERIES U L and or C S A recognized fuel gas and CO carbon monoxide detectors are rec ommended in all applications and their installation should be in accordance with the manuf...

Page 2: ...Air Cleaner 30 Humidifier 30 Filter 30 RXGW B01 Chimney Adapter 30 11 TWINNING 32 Furnace Twinning Installations 32 Control Boards 33 34 12 HIGH ALTITUDE 35 Natural Gas at High Altitudes 35 LP Gas at...

Page 3: ...umber is correct open the carton and verify that the furnace rating label specifies the same furnace model number that is speci fied on the carton label If the model numbers do not match re turn the f...

Page 4: ...hese publications are ANSI NFPA No 70 Latest Edition National Electrical Code NFPA90A Installation of Air Conditioning and Ventilating Sys tems NFPA90B Installation of warm air heating and air conditi...

Page 5: ...erature rise in heat record air temperature rise ______ Air temperature rise in cool record air temperature rise VENTING ______ Correct vent pipe diameter and length according to NFGC tables _________...

Page 6: ...IF THE FURNACE IS A MULTI STAGE FURNACE WARNING USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE REFER TO THE FURNACE RATING PLATE WARNING NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE A COMM...

Page 7: ...AS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE IF AIR MOVING...

Page 8: ...SITE SELECTION 1 Select a site in the building near the center of the pro posed or existing duct system 2 Give consideration to the vent system piping when se lecting the furnace location Be sure the...

Page 9: ...PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROP ERTY DAMAGE PERSONAL INJURY OR DEATH THE HOMEOWNER SHOULD BE CAUTIONED THAT...

Page 10: ...REQUIRE 3 TO 4 OR 3 TO 5 ADAPTER 4 ADAPTER INCLUDED WITH 801P UNITS MAY BE 0 WITH TYPE B VENT MAY BE 1 WITH TYPE B VENT LEFT SIDE REDUCED CLEARANCE IN SHIP WGTS FIGURE 4 UPFLOW HORIZONTAL DIMENSIONS L...

Page 11: ...Where the maximum airflow is 1800 CFM or more BOTH sides or the bottom must be used for the return air Do not take return air from the back of the unit NOTE DO NOT take return air from furnace rooms g...

Page 12: ...M FLANGES OF CABINET BEFORE THE UNIT IS INSTALLED LIFT UP PULL OUT 1 REMOVE 2 SCREWS LIFT BASE UP SLIDE FORWARD TO REMOVE 2 INSTALLATION IS REVERSE OF REMOVAL VERIFY REAR FLANGE IS SEALED PROPERLY AS...

Page 13: ...stion gases from an adjacent fuel burning appliance NOTE Do not block furnace access with support rods Main tain clearances recommended in Figure 8 Allow enough space for proper service maintenance or...

Page 14: ...of all appliances in the space If the open space contain ing the appliances is in a building with tight construction contem porary construction outside air may still be required for the appliances to...

Page 15: ...inch of free area for each 1 000 BTUH of total input in the space Table 2 shows some typical examples of openings required for com bustion air openings required for a confined space B USING OUTDOOR AI...

Page 16: ...EN TWO OPENINGS ARE USED WITH A FURNACE 1 LOCATED IN A CONFINED SPACE 2 USING OUTDOOR AIR FOR COMBUSTION 3 COMMUNICATING DIRECTLY TO THE 3 OUTSIDE THROUGH AN OPENING OR 3 THROUGH A VERTICAL DUCT 16 Co...

Page 17: ...OT A REQUIREMENT SEE PREVIOUS PAGE SINGLE ELBOW IS ALLOWED BUT MAY NOT PREVENT DEBRIS FROM BEING DROPPED INTO THE FURNACE GROUND OR SHELF SURFACE 6 MIN 6 MININUM CLEARANCE PVC DOUBLE ELBOW 8 SCREWS ME...

Page 18: ...attic must be ventilated by gable or soffit vents COMBUSTION AIR FROM ATTIC If attic combustion air is used the inlet air opening at the furnace must be protected from accidental blockage Install a 9...

Page 19: ...nstallation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this man ual Single wall vent connectors to B 1 vent or masonry chimneys may be u...

Page 20: ...s 16 and 17 5 Any angle greater than 45 degrees from the vertical is consid ered horizontal The total horizontal distance of a vent plus the horizontal vent connector serving draft hood equipped appli...

Page 21: ...URE 17 FIGURE 18 DEDICATED VENTING THROUGH CHIMNEY WITH B 1 VENT FRESH AIR INLET ST A1220 09 X0 1 STANDARD 3 FLUE CONNECTION ALL MODELS 2 4 ADAPTER 801P MODELS ONLY SEE NATIONAL FUEL GAS CODE FOR SIZI...

Page 22: ...venting system NOTE Ensure existing venting system complies with latest addi tion of National Fuel Gas Code ANSI Z223 1 and all local codes regulations 1 Visually inspect the venting system for prope...

Page 23: ...N AIR AND TENDS TO COLLECT AT LOWER LEVELS MAKING IT MORE DIFFICULT TO SMELL AT NOSE LEVEL NATURAL GAS IS LIGHTER THAN AIR AND WILL RISE POSSIBLY ACCUMULATING IN HIGHER PORTIONS OF THE STRUCTURE IF A...

Page 24: ...3 feet to easily remove the control valve assembly Install a manual shut off valve in the gas line outside the furnace cas ing The valve should be readily accessible to turn the gas supply on or off I...

Page 25: ...RIFICES MAY OR MAY NOT NEED TO BE CHANGED SEE THE SECTION TITLED HIGH ALTITUDE INSTALLATIONS OF THIS BOOK FOR INSTRUCTIONS FIGURE 20 TYPICAL GAS VALVE HONEYWELL REGULATOR CAP WARNING NEVER PURGE A GAS...

Page 26: ...remove any restrictions in the gas supply piping or enlarge the gas pipe See Tables 7 and 8 With LP gas have the LP supplier adjust the line pressure at the regulator Manifold Gas Pressure Measurement...

Page 27: ...r and the gas supply to the furnace 2 Remove the burner door from the furnace 3 Remove the burner assembly handle with care 4 Remove the two screws attaching the NOx insert retainer bracket to the cen...

Page 28: ...lly connected to line volt age prior to reversing the electrical connection 2 Disconnect the wires from the door switch 3 Remove the junction box from the furnace cabinet wall by re moving the two scr...

Page 29: ...e sized as shown NOTE Do not use 24 volt control wiring smaller than No 18 AWG Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat Run the thermo...

Page 30: ...the induced draft motor is ener gized NOTE Maximum current 1 0 amps for each option humidifier or electronic air cleaner FILTERS See Figure 25 Keep filters clean at all times A filter is not provided...

Page 31: ...HE FURNCE AT THE LOCATIONS PROVIDED CUT OUT USING EMBOSSED ANGLES AS A GUIDE FOR PROPER SIZE 23 X 14 ST A1220 07 00 RXGF CB 6625 7 5 5 FIELD SUPPLIED FILTER ST A1220 06 X0 FIGURE 25 FILTER LOCATIONS A...

Page 32: ...eating cooling or fan NOTE Duct system must be adequate to provide correct airflow to each furnace for supply and return UT ELECTRONIC CONTROLS 1194 200 CONTROL BOARD 62 104058 02 1 Single Stage Opera...

Page 33: ...ILL FLASH TO INDICATE A TWINNING PROBLEM CONFIRM PROPER WIRING IF THIS FAULT IS PRESENT TWINNING CONTROL BOARDS FIGURE 26 UT ELECTRONIC CONTROLS 1194 200 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE...

Page 34: ...34 R Y G W2 W1 COOLING CONTACTOR FIGURE 27 UT ELECTRONIC CONTROLS 1194 200 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION TWINNING CONTROL BOARDS cont THERMOSTAT ST A1194 25 2 STAGE Twinning...

Page 35: ...Sea Level Heating Value 1050 Q 23 81 ft3 Natural Gas per hour From Table F 1 of Natural Fuel Gas Code Handbook 2002 3 5 w c column Orifice required at Sea Level 43 From Table F 4 of National Fuel Gas...

Page 36: ...90 FURNACE MODEL NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE ELEVATION Table is derived from Appendix of the National Fuel Gas Code To determine the correct orifice for your installation con...

Page 37: ...e LP orifices are based on an 11 of water column pressure at the orifice which dif fers from products that use 10 of water column at the orifice This difference requires a deviation from the NFGC orif...

Page 38: ...gnition 4 The spark igniter is energized to light the gas burners and stays energized for the up to 7 seconds after the gas valve opens 5 8 seconds after the gas valve opens the remote flame sen sor m...

Page 39: ...n has occurred four times in a row the control enters one hour lockout and fault codes 10 and 11 will be displayed alternately as described above 2 When flame is lost five times in a row the control e...

Page 40: ...our period will commence after flame is no longer detected Dead Blower has been detected main limit circuit open for more than 150 seconds When voltage has unexpectedly been detected on the gas valve...

Page 41: ...tting of the SW1 dipswitch is OFF The factory setting display orientation is with the control placed in a vertical orientation and the low volt age terminal block T2 is in the bottom position Heat Blo...

Page 42: ...cleared from the fault buffer after one week The fault buffer can also be manually cleared if this is de sired For the first 30 seconds after a change in state of dip switch SW4 the furnace control wi...

Page 43: ...er orifices To change orifice spuds shut off the manual gas valve and re move the gas manifold On LP gas furnaces the LP gas supply pressure must be set between 11 and 13 w c by means of the tank or b...

Page 44: ...local gas utility to obtain the yearly average heating value and orifice size required to fire each individual burner at 25 000 BTU HR NOTE Refer to the High Altitude Section of this manual and the Na...

Page 45: ...ge either the air flow is too much or the manifold pres sure needs to be adjusted Use lower speed tap on the multi speed blower IMPORTANT The measured temperature rise should be in the middle of the r...

Page 46: ...ACE BEFORE ATTEMPTING TO CHANGE THE BLOWER SPEED FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN SEVERE PERSONAL INJURY OR DEATH Low 823 803 787 732 718 691 651 593 Med Lo 1030 1018 1006 976...

Page 47: ...be called to diagnose and or correct the source of tripping If this unit is mounted in a closet the door must be closed when making this check PRESSURE SWITCH This furnace is equipped with a normally...

Page 48: ...nd through it to keep from overheating CAUTION DO NOT OPERATE THE SYSTEM FOR EXTENDED PE RIODS WITHOUT FILTERS A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND...

Page 49: ...replacement marking which can be obtained through the distributor if any are found to be illegible or missing REPLACEMENT PARTS Please visit www myrheem com myruud com for replace ment parts informati...

Page 50: ...d range ROLLOUTS ensure rollouts or overtemperature limits do not need to be reset Make sure no flame rollout in burner compartment due to blocked flu or heat exchanger OVERFIRE ensure furnace is not...

Page 51: ...51 Wiring Diagram FIGURE 32 FOR MODELS WITH UT ELECTRONIC CONTROLS 1028 928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION...

Page 52: ...52 CM 0114...

Reviews: