Ruijie RG-NBS3100 Series Switches Hardware Installation and Reference Guide 

 

Preparation before Installation 

 

20 

 

when the relative humidity is low, not only affecting the useful life of the equipment, but also causing communication 

faults. Table 2-2 shows the requirements for the dust content and granularity in the equipment room. 

Table 2-2 Requirements for the Dust Content and Granularity in the Equipment Room 

Dust 

Unit 

Density 

Diameter

0.5

μ

Particles/m

3

 

3.5

×

10

6

 

Diameter

5

μ

Particles/m

3

 

3

×

10

4

 

Apart from dust, the salt, acid and sulfide in the air in the equipment room must also meet strict requirements, as such 

poisonous substances may  accelerate  the corrosion  of  the metal  and  the aging of some parts.  The  equipment  room 

should be protected from the intrusion of harmful gases such as sulfur dioxide, sulfured hydrogen, nitrogen dioxide, and 

chlorine), whose requirements are listed in Table 2-3. 

Table 2-3 Requirements for Harmful Gases in the Equipment Room 

Gas 

Average (mg/m3) 

Maximum (mg/m3) 

SO

2

 

0.3  

1.0  

H

2

0.1  

0.5  

NO

2

 

0.5  

1.0 

Cl

2

 

0.1  

0.3   

 

Both average and maximum value are measured for a week. The switch cannot be placed in the environment with 

the maximum density for over 30 minutes every day. .. 

2.2.4  Interference Resistance 

The switch 

is vulnerable to external interface caused by capacity coupling, inductance coupling, electromagnetic wave 

radiation,  common  impedance  (including  grounding  system)  coupling  and  conducting  wires  (including  power  cords, 

signal and output wires).

 

Therefore, the following points should be noted:

 

 

The AC power supplying system is the TN system. The single-phase three-wire socket with protecting grounding 

must be  used as  the  socket  for  the  power  s

upply to enable the device’s upper filter circuit to effective filter the 

power interface.

 

 

The  switch 

should  be  far  from  high-power  radio  transmitting  stations,  radar  stations  and  high-frequency  and 

large-current devices.

   

 

Electromagnetic shielding methods should be applied when necessary, such as using the shielded cable as the 

interface cable.

 

 

Cables must be connected to interfaces inside the room to prevent damage to the device’s signal ports caused by 

over-voltage and over-current generated by thunder and lightning.

   

2.2.5  Grounding 

A good grounding system is the basis for the stable and reliable operation of the RG-NBS3100 series switches. It is the 

chief condition to prevent lightning stroke and resist interference. Please carefully check the grounding conditions on 

the installation site according to the grounding requirements, and perform grounding operations properly as required. 

 

Effective  grounding  of  the  switch  is  an  important  guarantee  for  lightning  protection  and  interference  resistance. 

Therefore, connect the grounding line of the switch properly. 

Safety Grounding 

Summary of Contents for RG-NBS3100 Series

Page 1: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide...

Page 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Page 3: ...ite https www ruijienetworks com Technical Support Website https ruijienetworks com support Case Portal https caseportal ruijienetworks com Community https community ruijienetworks com Technical Suppo...

Page 4: ...wnward compatible with 100Base FX 1000Base T is downward compatible with 100Base TX and 10Base T 1 1 RG NBS3100 24GT4SFP Technical Specifications Model RG NBS3100 24GT4SFP CPU Built in CPU single core...

Page 5: ...61000 3 3 EN 55035 ETSI EN 300 386 Security Standards GB4943 2011 EN 62368 1 Dimensions W x D x H 440 mm x 165 mm x 44 mm Weight 2 4 kg The RG NBS3100 24GT4SFP switch is a class A product In a domest...

Page 6: ...the separate protective earthing terminal The device installation shall be permanently connected to building earth by a skilled person The device shall be intended to be used in a location having equ...

Page 7: ...cal Specifications Model RG NBS3100 24GT4SFP P CPU Built in CPU single core processor 500MHz Flash Memory 16 MB SDRAM DDRIII 256MB Optical Module See Appendix B The copper cable is not supported The s...

Page 8: ...RG NBS3100 24GT4SFP P switch is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures The high tempera...

Page 9: ...he LED is solid green it indicates that the PoE supported ports are supplying power when the LED blinks green the power of the ports is overloaded Back Panel Figure 1 6 Back Panel of RG NBS3100 24GT4S...

Page 10: ...f The port is not connected Solid green The port is connected at 10 100 1000 Mbps Blinking green The port is receiving or transmitting traffic at 10 100 1000 Mbps RJ45 port PoE status LED 1 24 Off PoE...

Page 11: ...d Power Consumption 8W Temperature Operating temperature 0 C to 50 C Storage temperature 40 C to 70 C Humidity Operating humidity 10 to 90 RH Storage humidity 5 to 95 RH Fan Not supported Temperature...

Page 12: ...00 8GT2SFP Front Panel Figure 1 9 Front Panel of RG NBS3100 8GT2SFP Note 1 System status LED 2 Reset button 3 10 100 1000 Base T Ethernet port 4 Copper port status LED 5 1000 Base X SFP port 6 SFP por...

Page 13: ...air circulation It is recommended to clean the device once every 3 months to avoid dust from blocking vents LED LED Panel Identification State Meaning System status LED Status Off The switch is not re...

Page 14: ...PoE Supports PoE and PoE Ports 1 8 are PoE capable with the maximum power output of 30W per port Port 9 does not support PoE The overall maximum output power of PoE PoE is 125W PoE Mode Mode A data pa...

Page 15: ...d be installed in the restricted area when the ambient temperature exceeds 50 deg C Product Appearance On the front panel the RG NBS3100 8GT2SFP P Ethernet switch provides 8 10 100 1000Base T Ethernet...

Page 16: ...a skilled person The device shall be intended to be used in a location having equipotential bonding such as a telecommunication centre a dedicated computer room or a restricted access area Heat Dissi...

Page 17: ...lation Keep the chassis clean and free from dust Do not place the equipment in a passage Do not wear loose clothes or any other things that may be caught by the chassis during installation and mainten...

Page 18: ...eakage protector divided by two is greater than the sum of maximum leakage currents of all the power supplies The rated leakage non action current of a leakage protector shall be 50 of the leakage act...

Page 19: ...the equipment may be damaged In an environment with high relative humidity the insulating material may have bad insulation or even leak electricity Sometimes the materials may suffer from mechanical...

Page 20: ...caused by capacity coupling inductance coupling electromagnetic wave radiation common impedance including grounding system coupling and conducting wires including power cords signal and output wires T...

Page 21: ...tection system of a facility is an independent system that consists of the lightning rod download conductor and the connector to the grounding system which usually shares the power reference ground an...

Page 22: ...er Radiated interference may affect any signal path in the equipment and is difficult to shield For the AC power supply system TN single phase three core power socket with protective earthing conducto...

Page 23: ...re installation please confirm the following points Whether ventilation requirements are met for the switch Whether the requirements of temperature and humidity are met for the switch Whether power ca...

Page 24: ...pted For example use interface cables to shield cables 100 meter network cables should be laid inside the equipment room and outdoor cabling of such cables is prohibited If outdoor cabling is necessar...

Page 25: ...Port Switch Figure 3 5 Attaching the Brackets to the Rack 24 Port Switch Figure 3 6 Attaching the Brackets to the Rack 24 Port Switch 3 3 2 Mounting the Switch on a Table Attach the four rubber pads...

Page 26: ...aximum current Cables of good conductor should be used Do not use bare wire The grounding electric resistance should be less than 1 To guarantee the security of the body and the device the switch must...

Page 27: ...fibers at the connectors have natural bends or bends of large radius Do not bundle fibers and twisted pairs too tightly as this may press hard the fibers and affect their service time and transmission...

Page 28: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide Product Installation 28 Check that sufficient airflow is available around the device over 10 cm...

Page 29: ...d RJ 45 port of the network cable to any Ethernet port of the switch Configuring the Device Step 1 Start the PC and configure the IP address of the PC as 10 44 77 XXX 10 44 77 XXX indicates the IP add...

Page 30: ...the parameters are already configured Checking after Power on Recommended After power on you are recommended to perform the following checks to ensure the normal operation of follow up configurations...

Page 31: ...port is not in connectivity or it is erroneous in receiving transmitting frames The connected twisted pair cable is faulty The length of the cable exceeds 100 m The port has special configuration tha...

Page 32: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide Troubleshooting 32 that rated of the optical module appropriate length...

Page 33: ...BASE T port uses four pairs of wires for transmission all of which must be connected Figure A 1 shows the connections of the twisted pairs used by the 1000BASE T port Figure A 1 Schematic Diagram for...

Page 34: ...and Connection Media 34 Optical Fiber Connection For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The connection s...

Page 35: ...ransmitted Light dBm Intensity of Received Light dBm Min Max Min Max MINI GBIC SX MM8 50 850 MMF No 9 5 3 17 0 MINI GBIC LX SM13 10 1310 SMF No 9 5 3 20 3 GE eSFP SX MM85 0 850 MMF Yes 9 5 3 17 0 GE e...

Page 36: ...MF 50 125 500m GE SFP SX SM1550 BIDI LC MMF 50 125 500m GE SFP LX20 SM1310 BIDI LC SMF 9 125 20km GE SFP LX20 SM1550 BIDI LC SMF 9 125 20km GE SFP LH40 SM1310 BIDI LC SMF 9 125 40km GE SFP LH40 SM1550...

Page 37: ...Module 37 Rate Distance Module Pairs 1000M 500m GE SFP SX SM1310 BIDI GE SFP SX SM1550 BIDI 1000M 20km GE SFP LX20 SM1310 BIDI GE SFP LX20 SM1550 BIDI 1000M 40km GE SFP LH40 SM1310 BIDI GE SFP LH40 SM...

Page 38: ...cal requirement Precautions for installation Make sure that the PE terminal of the power arrester has been well grounded After connecting the switch AC power plug to the socket of the power arrester l...

Page 39: ...to check whether the grounding line for the arrester is in good contact with the switch grounding terminal and the framework According to the description on the Ethernet Port Arrester Hardware Instal...

Page 40: ...to the OUT end Poor arrester grounding The length of the grounding line should be as short as possible to ensure that it is in good contact with the switch grounding terminal Use the multimeter to con...

Page 41: ...erall diameter The minimum bend radius of a coaxial cable should be 7 times the overall diameter of the cable If the cable is constantly bent plugged or unplugged the bend radius should be 10 times th...

Page 42: ...proper cable ties to bind cables together Do not tie two or more cable ties to bind cables Cut off excess cable tie cleanly with no sharp edges after bundling cables as shown in Figure D 2 Figure D 2...

Page 43: ...ed and prevented from loosening as shown in Figure D 4 Figure D 4 Fastening Cable Lugs Note Flat washer Nut Spring washer Flat washer When using a stiff cable fix it near the cable lug to avoid stress...

Page 44: ...conditions such as windstorm and heavy rain as well as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the resid...

Page 45: ...Ruijie RG NBS3100 Series Switches Hardware Installation and Reference Guide 45...

Reviews: