Temperature/Humidity Requirements   

To ensure normal operation and prolong the service life of the device, the equipment room must maintain constant 

temperature and humidity. If the equipment room is overheated for a long time, the insulation materials may result in 

defective insulation and even electric leakage. If the relative humidity is low, the insulation spacer may result in dry 

shrinkage, which will make screws looser and easily generate static electricity in the dry environment, thus damaging the 

interior circuits on the device. Excessively high temperature will accelerate the aging of insulation materials and 

compromise the reliability and even service life of the device. The temperature/humidity requirements are shown below 

(detailed difference between products is described in the chapter of "Product Overview"):     

 

Table 2-1 Temperature and Humidity Requirements of Ruijie EG Series Breakout Gateways 

Temperature   

Relative Humidity   

Long-term working 

condition   

Short-term working 

condition 

Long-term working 

condition 

Short-term working 

condition 

15ºC to 30ºC/ 59ºF to 86ºF  0ºC to 45ºC/ 32ºF to 113ºF  40% to 65% 

10% to 90% 

 

 

The temperature/humidity of working atmosphere indicates the value measured at 1.5 m above the floor and 

0.4 m ahead of the equipment frame when there is no protection plate on the front and rear side of the 

equipment frame.     

 

Short-term working condition refers to the continuous operation no exceeding 48 hours or accumulative 

operations no exceeding 15 days in a year.     

 

Extremely harsh working environment generally refers to the ambient temperature and humidity which may 

be encountered when the equipment room air-conditioning system fails but will recover in less than 5 hours 

every time.   

Cleanliness Requirements   

The dust is also a major threat to the safe operation of device. The dust accumulated on the device may cause 

electrostatic adsorption and result in poor contact. It will not only compromise the service life of device but also cause 

communication failure. When the indoor relative humidity is low, such electrostatic adsorption will incur more easily.     

 

Table 2-2 The Equipment Room Dust Content and Particle Size Requirements of Ruijie EG Series Breakout 

Gateways     

Maximum Di

ameter (μm) 

0.5   

1   

3   

5   

Maximum Density (Particles/m3) 

1.4 x 10

7

 

7 x 10

5

   

2.4 x 10

5

   

1.3 x 10

5

   

Apart from the dust, the device is also sensitive to the hydrochloric acid sulfide contained in the air. These noxious gases 

will accelerate metal wastage and the aging of certain parts. The upper limits of noxious gases (Sulfur dioxide, Sulfured 

hydrogen, Nitrogen dioxide, Ammonia and Chlorine) in the equipment room are shown in Table 2-3:     

 

Table 2-3 Upper Limits of Noxious Gases of Ruijie EG Series Breakout Gateways 

Summary of Contents for EG3250

Page 1: ...RG EasyGate Series Hardware Installation Guide V1 60 RG EasyGate Series Products Hardware Installation and Reference Guide V1 60...

Page 2: ...this document in any form or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subje...

Page 3: ...stance Ruijie Networks Website https www ruijienetworks com Technical Support Website https ruijienetworks com support Case Portal http caseportal ruijienetworks com Community http community ruijienet...

Page 4: ...configuration commands can easily use this product without training Ruijie EG Series Breakout Gateways Ruijie EG3250 Breakout Gateway Appearance of Ruijie EG3250 Breakout Gateway Figure 1 1 Front Pan...

Page 5: ...232 Dimension W x H x D 440mm x 43 6mm x 200mm excluding the foot pad Voltage 100VAC to 240VAC 50 60 Hz 0 65A Power Consumption Less than 25W Working Environment Temperature 0 C to 45 C 32 F to 113 F...

Page 6: ...t Gateway Full Support to Extensive Protocols Ruijie EG series breakout gateway is applicable to different network environment as it provides full support to extensive protocols Providing RJ45 port an...

Page 7: ...nd user based real time flow analyzer provides detailed information on source destination IP address service port application protocol session number and flow size Supporting user source IP address de...

Page 8: ...e and other deployment modes meeting the need for deployment in various contexts The transparent bridging does not change the configurations of other devices allowing complete URL filtering flow contr...

Page 9: ...he clock If the clock is not set the time may not be correct if the clock has been set precisely and the time is still incorrect the built in button cell of device may have ran out which is typically...

Page 10: ...4 m ahead of the equipment frame when there is no protection plate on the front and rear side of the equipment frame Short term working condition refers to the continuous operation no exceeding 48 ho...

Page 11: ...bag When observing or transferring the circuit board of breakout gateway touch the outer edge of circuit board and avoid direct contact with the components on the circuit board Anti Interference Requ...

Page 12: ...essories Make sure the cabinet and workbench is properly grounded Installation Tools and Devices To enable smooth installation prepare the following items Installation tools Connecting cables Related...

Page 13: ...reserve a heat elimination room of 10 cm around the device Do not place heavy things on the device Installing Power Cables The requirements of Ruijie EG series breakout gateway products on AC power s...

Page 14: ...attributes of a console are shown in Table 3 1 In case of WEB based configuration the console port will be of no use Table 3 1 Attributes of the Console Connection Parameter Description Connector RJ 4...

Page 15: ...connected and whether the microcomputer or terminal for gateway configuration is started or configured Before powering on the breakout gateway be aware of the location of the power switch of the break...

Page 16: ...LED indicators If abnormity occurs perform the following checks Whether the power switch is turned on Whether the power supply of the breakout gateway is turned on Whether the power cable is properly...

Reviews: