Ruijie  5/8-Port  Plastic  Series  Switches  Hardware  Installation  and  Reference  Guide 

 

 

In an environment with low relative humidity, however, the insulating strip may dry and shrink. Static electricity may 

occur easily and endanger the circuit on the equipment. 

 

In an environment with high temperature, the equipment is subject to even greater harm, as its performance may 

degrade significantly and various hardware faults may occur.   

Therefore, the ambient temperature and humidity of the 5/8-port plastic series switch must meet the requirements listed in 

Table 2-1. 

Table 2-1 Temperature and Humidity Requirements of the 5/8-Port Plastic Series Switch 

Temperature 

Relative Humidity 

0

  to 40

 

(32°F to 104°F) 

10% to 90% 

 

 

The requirements for the sampling site of the temperature and humidity in the operating environment of the device 

are as follows: 

 

The vertical height is 1.5 m above the floor. 

 

The distance from the front panel of the equipment is 0.4 m. 

2.2.3  Cleanness 

Dust poses a severe threat to the running of the equipment. The indoor dust falling on the equipment may be adhered by 

the static electricity, causing bad contact of the metallic joint. Such electrostatic adherence may occur more easily when 

the relative humidity is low, not only affecting the useful life of the equipment, but also causing communication faults. Table 

2-2 shows the requirements for the dust content and granularity in the equipment room. 

Table 2-2 Requirements for the Dust Content and Granularity in the Equipment Room 

Dust 

Unit 

Density 

Diameter

0.5

μ

Particles/m

3

 

3.5

×

10

6

 

Diameter

5

μ

Particles/m

3

 

3

×

10

4

 

Apart from dust, the salt, acid and sulfide in the air in the equipment room must also meet strict requirements, as such 

poisonous substances may accelerate the corrosion of the metal and the aging of some parts. The equipment room should 

be protected from the intrusion of harmful gases such as sulfur dioxide, sulfured hydrogen, nitrogen dioxide, and chlorine), 

whose requirements are listed in Table 2-3. 

Table 2-3 Requirements for Harmful Gases in the Equipment Room 

Gas 

Average (mg/m

3

Maximum (mg/m

3

SO

0.3 

1.0 

H

2

0.1 

0.5 

NO

2

 

0.5 

1.0 

Cl

2

 

0.1 

0.3 

 

Both average and maximum value are measured for a week. The switch cannot be placed in the environment with 

the maximum density for over 30 minutes every day. .. 

Summary of Contents for RG-ES05

Page 1: ...Ruijie Reyee 5 8 Port Plastic Series Switches Hardware Installation and Reference Guide...

Page 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Page 3: ...om Technical Support Website https ruijienetworks com support Case Portal https caseportal ruijienetworks com Community https community ruijienetworks com Technical Support Email service_rj ruijienetw...

Page 4: ...ase T 1 1RG ES05 Technical Specifications Model RG ES05 Ports Supports 5 10 100 Base TX auto sensing Ethernet ports Power Supply AC input Rated voltage range 100 VAC to 240 VAC Maximum voltage range 9...

Page 5: ...Dimensions W x D x H 108 1 mm x 64 mm x 24 8 mm 4 26 in x 2 52 in x 0 98 in Weight With Package 0 19 kg 0 42 lbs The RG ES05 switch is a class A product In a domestic environment this product may caus...

Page 6: ...blocking vents LEDs LED Panel Identification State Meaning System status LED Off The switch is powered off Solid on The switch is operational RJ45 port status LED 1 5 Off The port is not connected So...

Page 7: ...55032 2015 A11 2020 EN 55035 2017 A11 2020 EN 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 300 386 V2 1 1 2016 07 Security Standards GB4943 2011 EN 62638 1 Earth Leakage Current 1 5mA Dimensions W x D...

Page 8: ...DC power port Heat Dissipation The RG ES08 adopts natural heat dissipation thereby ensuring normal function of the device Maintain a minimum clearance of 100 mm 3 94 in around the device It is recomm...

Page 9: ...o 240 VAC Maximum voltage range 90 VAC to 264 VAC Frequency 50 60 Hz Rated current 0 3 A Adapter output Rated voltage range 5 VDC Rated current range 0 6 A EEE Not supported PoE Not supported Power Co...

Page 10: ...n Weight With Package 0 2 kg 0 44 lbs The RG ES05G switch is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequa...

Page 11: ...blocking vents LEDs LED Panel Identification State Meaning System status LED Off The switch is powered off Solid on The switch is operational RJ45 port status LED 1 5 Off The port is not connected Sol...

Page 12: ...32 2015 A11 2020 EN 55035 2017 A11 2020 EN 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 300 386 V2 1 1 2016 07 Security Standards GB4943 2011 EN 62638 1 Earth Leakage Current 1 5mA Dimensions W x D x H...

Page 13: ...pation The RG ES08G adopts natural heat dissipation thereby ensuring normal function of the device Maintain a minimum clearance of 100 mm 3 94 in around the device It is recommended to clean the devic...

Page 14: ...uijie 5 8 Port Plastic Series Switches Hardware Installation and Reference Guide Solid on The port is connected at 10 100 1000 Mbps Blinking The port is receiving or sending traffic at 10 100 1000 Mbp...

Page 15: ...be qualified Before installing the device carefully check any potential danger in the surroundings such as damp wet ground or floor Before installing the device find out the location of the emergency...

Page 16: ...r less than 30mA human body safety current is 30mA When twice of the total leakage current of the system is greater than 30mA the system must be equipped with two or more leakage protectors For the le...

Page 17: ...on the equipment may be adhered by the static electricity causing bad contact of the metallic joint Such electrostatic adherence may occur more easily when the relative humidity is low not only affec...

Page 18: ...from the electromagnetic wire or signal cable connection between the source and the sensitive component along which cable the interference conducts from one unit to another Conducted interference ofte...

Page 19: ...les should be laid inside the equipment room and outdoor cabling of such cables is prohibited If outdoor cabling is necessary take relevant measures for lightning protection 3 2 1 Mounting the Switch...

Page 20: ...a table as shown in Figure 3 2 Figure 3 2 Placing the Switch on a Table The device must be installed and operated in the place that can restrict its movement 3 3Checking after Installation Before che...

Page 21: ...add it to the topology If the unmanaged switch is already added to the topology and displayed as a virtual device Select the virtual device and scan its QR code or manually enter its information to t...

Page 22: ...Adding Unmanaged Device Manually 1 Tap Topology to enter the topology page 2 Tap the Topology button and select the existing managed device To add an unmanaged downlink switch manually select Manually...

Page 23: ...Ruijie 5 8 Port Plastic Series Switches Hardware Installation and Reference Guide...

Page 24: ...correctly connected The power supply voltage complies with the requirement of the switch 4 1 2 Checking after Program Startup Recommended After power on you are recommended to perform the following c...

Page 25: ...er cable is in loose contact Check whether the power socket at the equipment room is normal and whether the power cable is plugged in The RJ45 port is not in connectivity or it is erroneous in receivi...

Page 26: ...uses four pairs of wires for transmission all of which must be connected Figure A 1 shows the connections of the twisted pairs used by the 1000BASE T port Figure A 1 Four Twisted Pairs of the 1000BASE...

Page 27: ...eference Guide Optical Fiber Connection For the optical fiber ports select single mode or multiple mode optical fibers for connection according to the fiber module connected The connection schematic d...

Page 28: ...Precautions for installation Make sure that the PE terminal of the power arrester has been well grounded After connecting the switch AC power plug to the socket of the power arrester lightning protect...

Page 29: ...her the grounding line for the arrester is in good contact with the switch grounding terminal and the framework 4 According to the description on the Ethernet Port Arrester Hardware Installation Guide...

Page 30: ...Poor arrester grounding The length of the grounding line should be as short as possible to ensure that it is in good contact with the switch grounding terminal Use the multimeter to confirm the contac...

Reviews: