Flex-Line
Installation manual
__________________________________________________________________________________
22
Thermal insulation of combustible environment
Floor
A combustible floor is protected by a
concrete slab
and
thermal insulation
. The thermal insulation must
have long-term thermal resistance. The concrete slab and the thermal insulation cover the entire cavity
within the covering seamlessly.
*based on country-specific requirements
Front-opening appliances
*The hot air inlet must be able to circulate under the appliance and the heat created diverted away.
Appliance
Including substructure and hot air*
Min 20 cm high
Excluding substructure
< 20 cm high
Thermal insulation
with mineral wool in accordance with Table 2
[cm]
Thermal insulation
with mineral wool in accordance with Table 2
[cm]
Violino 45x60
0
4
Violino 45x80
0
4
Violino 55x73
0
4
Violino 55x98
0
4
Violino 65x87
0
4
RIII 45x56x46
0
4
RIII 45x56x60
0
4
RIII 45x56x80
0
4
RIII 45x80x46
0
4
RIII 45x100x46
0
4
RIII 55x100x46
0
4
Fireplace insert
Adjustable foot
Floor
Thermal insulation
Casing
Precoat*
Concrete base with combustible environment *