40
English
Tel. +49 7930 9211-0 Fax +49 7930 9211-150
11. Modbus communication interface
11.1. Wiring diagram
11.2. Functions implemented
Function
code
Name
Description
03 Hex
Read Hold Register
Read device parameter
04 Hex
Read Input Register
Read current value
06 Hex
Write Single Register
Write device parameter word by word
10 Hex
Write Multiple Register
Write several device parameters word by word
Function
code
Name Sub-function Description
08 Hex
Return Query Dat
00
Send the received message back
08 Hex
Restart Communications 01
Restart communication
08 Hex
Force Listen Only Mode
04
Switch to listen-only mode
Fig. 26:
Control unit
120 Ohm Line
Place Jumper K 1 for the last
device on the bus
Signal line B with 10 kOhm
to GND
Signal line A with 10 kOhm to
+24 V
1.
Line
Summary of Contents for ETA K 1200 V W
Page 59: ...59 English www ruck eu Notes ...