RTR Energia 12kVAr Technical  User'S Manual Download Page 5

 

                       

TECHNICAL USER´S MANUAL

 

 
 

Thyristor modules  

Auxiliary Supply Conductor 
Cross Section 

mm

2

 

2.5 

2.5 

Fan Activation 
Temperature 

ºC 

50 

50 

Triggering Voltage/Current 

V/mA 

24/10 

24/10 

24/10 

24/10 

Triggering Conductor Cross 
Section 

mm

2

 

2.5 

2.5 

2.5 

2.5 

Overheating Protection 

ºC 

90±5 

90±5 

90±5 

90±5 

IP Class 

20 

20 

20 

20 

Ambient Temperature  
-Operating (Full Load) 
-Operating (%75 Load) 
-Storage 

 

ºC 
ºC 
ºC 

 

-20~45 
-20~60 

-40~100 

 

-20~45 
-20~60 

-40~100 

 

-20~45 
-20~60 

-40~100 

 

-20~45 
-20~60 

-40~100 

Relative Humidity 

5~95 

5~95 

5~95 

5~95 

Size (W x D x H) 

mm 

158x154x115 

158x154x115 

161x229x197.5 

161x229x197.5 

Weight 

kg / lb 

2.2 / 4.9 

2.2 / 4.9 

5.9 / 13.0 

5.9 / 13.0 

 

3 – Setup 

3.1 Prerequisites for Setup 

Modules should be mounted on the mounting plate through the mounting holes provided 

on  the  enclosure. 

Modules  must  be  mounted  vertically!  A  minimum  of  150mm  clearance  is 

imperative

 above and below to dissipate heat efficiently! 

Do not drill additional mounting holes 

on the device!

 Modules should be grounded through the mounting holes. 50kVAr and 80kVAr 

modules  may  also  be  grounded  through  connecting  the  ground  cable  to  the  auxiliary  power 
supply connector. 

Electrical connections should follow the wiring diagrams provided in Figures 3.3-3.6 in the 

Wiring  Diagrams  section. 

“Superfast”  electronic  branch  fuses  must  be  used  to  protect  the 

thyristor modules!

 

12kVAr and 25kVAr modules do not require an auxiliary voltage connection. These modules 

are  powered  internally.  The  50kVAr  and  80kVAr  modules  are  equipped  with  a  fan  and  are 
designed for forced cooling. 

Therefore, 50kVAr and 80kVAr modules require an auxiliary voltage 

(220V 50Hz) supply to power internal circuits and the cooling fan!

 

Modules can be instantaneously activated through a power factor correction relay, or any 

other compatible system, by applying a 10-24VDC trigger signal. Internal circuits are galvanically 
isolated from the trigger signal. 

Thyristor  modules  are  equipped  with  an  external  thermostat  terminal.  If  a  detuned  filter 

reactor  is  used  in  the  system,  the  user  may  attach  its  thermostat  to  the  external  thermostat 
terminal  on  the  module.  This  allows  the  module  to  protect  the  detuned  filter  reactor  from 
overheating. 

If this external thermostat connection is not used, user must short the thermostat 

connection terminals for the system to function properly! 

 

Summary of Contents for 12kVAr

Page 1: ...Ind Pinto Estaci n 28320 Pinto Madrid ESPA A Tel 34 916 916 612 Fax 34 916 912 257 info rtr es www rtr es Microprocessor Controlled Capacitor Switching Thyristor Modules Technical User s Manual Date 0...

Page 2: ...ratings specified in the technical specifications Do not touch the modules with bare and or wet hands while it is on Make sure that the power is turned off when cleaning Use a dry cloth to clean the m...

Page 3: ...1 1 General Description 1 2 Application Areas 2 Technical Specifications 3 Setup 3 1 Prerequisites for Setup 3 2 Installation 3 3 Wiring Diagrams 3 4 Ready for Start Up 3 5 Alarms and Indicators 4 Te...

Page 4: ...module internal memory The modules can operate with or without a detuned filter reactor The modules protect detuned filter reactors against overheating through their external thermostat connections Th...

Page 5: ...h connecting the ground cable to the auxiliary power supply connector Electrical connections should follow the wiring diagrams provided in Figures 3 3 3 6 in the Wiring Diagrams section Superfast elec...

Page 6: ...be equipped with a discharging High power resistors or discharge reactors are recommended to increase switching speed and frequency Discharge resistors need to be selected carefully to achieve desired...

Page 7: ...S MANUAL 6 Thyristor modules Figure 3 1 The effect of discharge resistance on discharge time for 7 189Hz and 14 134Hz detuned reactor PFC with three discharge resistors 7 rates may be used if no react...

Page 8: ...5 25kVAr 63 NH AC 690 25 50kVAr 125 NH AC 690 50 80kVAr 200 NH AC 690 80 MITIGATING HIGH di dt When the thyristors are triggered the current is initiated at the gate cathode junction The current sprea...

Page 9: ...ter reactors for 12kVAr 25kVAr 50kVAr and 80kVAr modules are presented in Figures 3 3 3 6 Figure 3 3 Recommended wiring diagram for 12kVAr and 25kVAr modules with a detuned filter reactor and a discha...

Page 10: ...r modules Figure 3 4 Recommended wiring diagram for 12kVAr and 25kVAr modules without a detuned filter reactor and with a discharge reactor Connection terminals wiring diagrams and structures of 12kVA...

Page 11: ...istor modules Figure 3 5 Recommended wiring diagram for 50kVAr and 80kVAr modules with a detuned filter reactor and a discharge reactor Connection terminals wiring diagrams and structures of 50kVAr an...

Page 12: ...r modules Figure 3 6 Recommended wiring diagram for 50kVAr and 80kVAr modules without a detuned filter reactor and with a discharge reactor Connection terminals wiring diagrams and structures of 50kVA...

Page 13: ...ults The function of each LED is described as follows POWER LED red Informs the user that the module is powered up FAULT LED red Informs the user of internal faults If the module detects a misconnecti...

Page 14: ...TECHNICAL USER S MANUAL 13 Thyristor modules Figure 4 1 12kVAr and 25kVAr modules technical drawings...

Page 15: ...TECHNICAL USER S MANUAL 14 Thyristor modules Figure 4 2 50kVAr and 80kVAr modules technical drawings...

Page 16: ...is used without wiring the thermostat connections Otherwise the module will evaluate this situation as a reactor thermal fault and will not let the user switch on the capacitors FAULT LED is blinking...

Page 17: ...ED displays operating status of the module If this LED is not lit up then one of the following four situations must be true 1 System is not powered up 2 Trigger signal is not being received 3 Capacito...

Page 18: ...he documentation delivered with the module and other relevant documentation Modules subjected to misuse negligence or accident In no event shall the manufacturer its suppliers or subcontractors be lia...

Reviews: