37
Properties
Processor
Select A, B, C, or E which will match the Node Processor to pull the information.
Online
This Bool variable will indicate if the selected 3200T/3201 Processor is operational
or not. If this variable is True, it indicates that the selected 3200T/3201 Processor
is online and operational.
Primary
This Bool variable will indicate if the selected 3200T/3201 Processor is the primary
Node Processor for host and peer-to-peer communications. If this variable is True,
it indicates that the selected 3200T/3201 Processor is responsible for direct
communications to host and peer-to-peer nodes.
I/O Errors
This Bool variable will indicate if any of the I/O cards configured in the application
program have errors. If this variable is True, at least one of the I/O card error
status word is indicating an error condition
Diagnostic Errors
This Bool variable will indicate if there are any errors in the 3200T system. If this
variable is True, errors exist.
Host Link Status
Bool variable will indicate any failure on the host communications link. If this
(2-Port, 4-Port)
This variable is True, it indicates normal communications on the host link,
Connector J1 is online. If variable value is equal to False, it indicates an
interruption in communications on the host link, Connector J1 is offline.
NOTE: If PTDB Device Monitor is enabled, the path from PTDB Computer to
Connector J1 must also be good to report True.
Interlink Link Status
This Bool variable will indicate any failure on the communications link between the
(2-Port, 4-Port)
Node Processors. If this variable is True, it indicates normal communications on
the interlink, Connector J2 is online. If the variable value is equal to False, it
indicates an interruption in communications on the link, Connector J2 is offline.
NOTE: This variable should be monitored only in 3200D, 3200T and 3200Q
SIS non-redundant Node is always False.