62
F14 - First-Up Group A
All alarms set to function F14 will operate as a single first-up group in accordance with the selected
first-up sequence. F14 is the function code allocated for first-up Group A.
FEATURE-F14
STATUS LED
Set to remove channel from first-up Group A
OFF
Set to include channel in first-up Group A
ON
F15 - First-Up Group B
All alarms set to function F15 will operate as a single first-up group in accordance with the selected
first-up sequence. F15 is the function code allocated for first-up Group B.
FEATURE-F15
STATUS LED
Set to remove channel from first-up Group B
OFF
Set to include channel in first-up Group B
ON
F16 - First-Up Group C (Four First-up Group version only)
All alarms set to function F16 will operate as a single first-up group in accordance with the selected
first-up sequence. F16 is the function code allocated for first-up Group C.
FEATURE-F16 (FOUR FIRST-UP GROUP VERSION ONLY)
STATUS LED
Set to remove channel from first-up Group C
OFF
Set to include channel in first-up Group C
ON
F16 – Alarm Input Selection (Standard version)
On standard units that have the communications capability enabled there are only two first-up groups
A and B. On these units Function 16 is used to configure how the communications operate.
With the communications option fitted it is possible to receive alarms in the normal way, from
volt-free contacts, or via the serial communications port. This function is used to select where the
system is looking to receive this alarm information. If the function is not selected then the normal
volt-free contacts are used. If the function is selected then the serial communications port will be
monitored for details of alarm status. It is possible to set this feature on an individual channel basis
hence having some alarm channels monitoring volt-free contacts and some monitoring the
communications.
FEATURE-F16 (STANDARD VERSION)
STATUS LED
Set to get alarm information from volt-free contact input
OFF
Set to get alarm information from the serial communications
ON
F17 - First-up Group D (Four First-up Group version only)
All alarms set to function F17 will operate as a single first-up group in accordance with the selected
first-up sequence. F17 is the function code allocated for first-up Group D.
FEATURE-F17 (FOUR FIRST-UP GROUP VERSION ONLY)
STATUS LED
Set to remove channel from first-up Group D
OFF
Set to include channel in first-up Group D
ON