60
A4:
Commons Card Remote Pushbutton Station
The total combined parameters of load and cables connected to Commons Card terminals
#5 to #8 and #12 must not exceed:
A5:
Alarm Card Connections
On the LN1000/12 the alarm card terminals are identified by the AL1 to AL6 (AL X) markings
on the backplane.
On the LN1000/32 the alarm card terminals are identified by the AL1 to AL8 (AL X) markings
on the top and the bottom backplanes.
Terminals AL X #7 and #8 must only be connected to AL X #1, by separate connections with
a maximum connection length of 100mm.
For each alarm card the total combined parameters of interconnecting cables and any
connected load for AL X terminals #1 to #6 and #9 to #12 must not exceed:
Group
Capacitance (uF)
Inductance (mH)
L/R Ratio
(uH/ohm)
IIC
14.5
320
2,080
IIB
43.5
660
6,240
IIA
116
2,560
16,640
Group
Capacitance (uF)
Inductance (mH)
L/R Ratio
(uH/ohm)
IIC
14.5
32
613
IIB
43.5
96
1,839
IIA
116
256
4,904