460 Gateway Device Line
460MXE
Scan List Settings
1) Data in values are values received from the Modbus slave device which are considered inputs to
BACnet.
2) Data out values are the values sent from the BACnet device to the Modbus slave.
3) The Point Type/Data Type values will match those of the Modbus slave device.
4) Length is the number of data types to be read. (It is not the number of registers)
5) Click Save.
6) A summary of the configured data will be displayed along with instructions in
red
to restart the de-
vice to save your changes. Click Restart.
7) A confirmation box will appear, click Restart Now. You will be redirected to the main page.