Real Time Automation, Inc.
20
1-800-249-1612
Modbus TCP/IP Server Data Group Configuration: Manual Mode
1)
To transition from either of the two Auto-Configure modes to Manual Configure Mode, click the
dropdown at the top of the Modbus TCP/IP server Configuration page and select Manual Configure.
a)
When prompted, click
OK
to confirm mode change or
Cancel
to remain in Auto-Configure Mode.
2)
Once OK is clicked, there are two options for how to proceed.
3)
To keep the data groups that are already configured, press
OK
.
a)
You would want this option if you are adding additional data groups or you want to modify the
data group(s) that already exist.
4)
To delete the data groups that are already there and start over, press
Cancel
.
5)
Enter the number of Read Data Groups and/or Write Data groups.
6)
Click the
Generate Data Groups
button to have the read and write data groups auto-generate for
you. You may manually configure the read and write data groups after they have been generated.