RS PRO IPT 1800 Instruction Manual Download Page 8

 

EN-6 

4-1 Voltage Measurement 

When the Loop and PSC Testers are first powered up by 
connecting them to the mains, they automatically display 
the  mains  voltage.  The  voltage  display  is  updated 
automatically  every  0.5s.    When  the  test  button  is 
depressed  (see  section  5.1  first)  the  voltage  mode  is 
cancelled.    To  recall  the  voltage  measurement  mode, 
the  power to  the instrument must be removed and  then 
restored again. 

4-2 Manual and Autotest 

Manual-Press and release the “Test Button”.    The result 
will be displayed for 3s and then the display will revert to 
zero. 

4-3 Automatic Overheat Cut-Out 

To test in accordance with the IEE regulations Loop and 
PSC  testers  may  dissipate  up  to  approximately  6kW  of 
energy during the test period, so that after repeated use 
the  test  resistor  may  overheat.    When  the  temperature 
reaches  a  level  that  may  damage  the  resistor  the 
instrument automatically locks out.    This is indicated by 
the  appropriate  over  temperature  symbol  in  the  digital 
display.   

When the resistor has cooled down, normal testing may 
continue. 
 

Summary of Contents for IPT 1800

Page 1: ...Instruction Manual IPT 1800 Digital LOOP PSC Tester FR EN IT DE ES P N P E...

Page 2: ...3 IV SPECIFICATIONS 4 4 1 Voltage Measurement 6 4 2 Manual and Autotest 6 4 3 Automatic Overheat Cut Out 6 V OPERATING INSTRUCTIONS 7 5 1 Correct Wiring 7 5 2 Measurement of the Loop Impedance 7 5 3 E...

Page 3: ...e to phase damage will result When conducting a test particularly on earth spikes do not touch any exposed metal work This is because the earth has a current flowing through it for the duration of the...

Page 4: ...easures low loop impedance resolution of 0 01 Ohm High impedance ranges permit direct measurements of ground spikes Automatic lock out if test resistor overheats Safe voltage measurement function Audi...

Page 5: ...EN 3 III INSTRUMENT LAYOUT P N P E AC CORD FI K EUR EATERNAL EARTH PROBE LCD DISPLAY...

Page 6: ...ction 240V 13A 6kA HRC ceramic fuses General Dimensions 180 L x 130 W x 70 H mm Weight Approx 800g include battery Test Current 25A approx 20Ohm Display Large style 3 1 2 digit custom LCD AC Test Peri...

Page 7: ...tegory 300V CAT single phase 230V Pollution Degree 2 This manual and product may use the following symbols adopted from International Safety Standards Equipment protected throughout by DOUBLE INSULATI...

Page 8: ...ual and Autotest Manual Press and release the Test Button The result will be displayed for 3s and then the display will revert to zero 4 3 Automatic Overheat Cut Out To test in accordance with the IEE...

Page 9: ...ON there is reversed phase and neon is ON there is reversed phase and neutral wiring 5 2 Measurement of the Loop Impedance Set the instrument to the 200 or 2000 range If the instrument is set to the 2...

Page 10: ...robe The phase earth loop impedance of exposed metal of bonding portable appliances or metal conduit etc can be tested using the external earth probe provided Connect the unit to the socket as normal...

Page 11: ...LCD with the appropriate units This will remain for 3s and then revert to zero An audible beep will sound on completion of the test For best results always test on the lowest possible range Note For l...

Page 12: ......

Reviews: