  Press  the  “Press  to  Test”  button.    The  value  of  loop 

impedance  will  be  displayed  with  the  appropriate  units.   
A bleep will sound on completion of the test. 

For best results always test on the lowest possible 
range. 

No harm will be done to the instrument by selecting too 
low a range. 

5-3 External Earth Probe 

The  phase  earth  loop impedance  of  exposed  metal  of 
bonding, portable appliances or metal conduit etc., can 
be tested using the external earth probe provided. 

Connect  the  unit  to  the  socket  as  normal.    Plug  the 
external  earth  probe  into  the  instrument.    This  breaks 
the  earth  continuity  at  the  socket  and  the  P-E  lamp 
should  go  out.    When  the  probe  is  connected  to  any 
other earth point the P-E lamp should light up. 

The point at which the probe is connected becomes the 
earth point (instead of at the socket). 

 

 
 

Summary of Contents for IPT 1800

Page 1: ...Instruction Manual IPT 1800 Digital LOOP PSC Tester FR EN IT DE ES P N P E...

Page 2: ...3 IV SPECIFICATIONS 4 4 1 Voltage Measurement 6 4 2 Manual and Autotest 6 4 3 Automatic Overheat Cut Out 6 V OPERATING INSTRUCTIONS 7 5 1 Correct Wiring 7 5 2 Measurement of the Loop Impedance 7 5 3 E...

Page 3: ...e to phase damage will result When conducting a test particularly on earth spikes do not touch any exposed metal work This is because the earth has a current flowing through it for the duration of the...

Page 4: ...easures low loop impedance resolution of 0 01 Ohm High impedance ranges permit direct measurements of ground spikes Automatic lock out if test resistor overheats Safe voltage measurement function Audi...

Page 5: ...EN 3 III INSTRUMENT LAYOUT P N P E AC CORD FI K EUR EATERNAL EARTH PROBE LCD DISPLAY...

Page 6: ...ction 240V 13A 6kA HRC ceramic fuses General Dimensions 180 L x 130 W x 70 H mm Weight Approx 800g include battery Test Current 25A approx 20Ohm Display Large style 3 1 2 digit custom LCD AC Test Peri...

Page 7: ...tegory 300V CAT single phase 230V Pollution Degree 2 This manual and product may use the following symbols adopted from International Safety Standards Equipment protected throughout by DOUBLE INSULATI...

Page 8: ...ual and Autotest Manual Press and release the Test Button The result will be displayed for 3s and then the display will revert to zero 4 3 Automatic Overheat Cut Out To test in accordance with the IEE...

Page 9: ...ON there is reversed phase and neon is ON there is reversed phase and neutral wiring 5 2 Measurement of the Loop Impedance Set the instrument to the 200 or 2000 range If the instrument is set to the 2...

Page 10: ...robe The phase earth loop impedance of exposed metal of bonding portable appliances or metal conduit etc can be tested using the external earth probe provided Connect the unit to the socket as normal...

Page 11: ...LCD with the appropriate units This will remain for 3s and then revert to zero An audible beep will sound on completion of the test For best results always test on the lowest possible range Note For l...

Page 12: ......

Reviews: