RS PRO IPT 1800 Instruction Manual Download Page 3

 

EN-1 

I. 

WARNING 

  This  instrument  must  only  be  used  by  a  competent, 

trained  person  and  operated  in  strict  accordance  with 
the  instructions.    We  will  not  accept  liability  for  any 
damage  or  injury  caused  by  misuse  or  non-compliance 
with the instruction or safety procedures. 

  It  is  essential  to  read  and  understand  the  safety  rules 

contained  in  the  instructions.    They  must  always  be 
observed when using the instrument. 

  This  instrument  is  only  intended  for  single  phase 

operation,  230V

±

10%  AC  phase  to  earth  or  phase  to 

neutral operation.    It must never be connected phase to 
phase-damage will result. 

 When conducting a test, particularly on earth spikes, do 

not touch any exposed metal work.    This is because the 
earth has a current flowing  through  it for the duration  of 
the test (approx. 20ms). 

  Never  open  the  instrument  case  -  there  are  dangerous 

voltages present. 

  This  instrument  is  primarily  protected  by  HRC  Ceramic 

fuses.    DO NOT  ATTEMPT to replace them if they fail.   
Should  they  fail  please  consult  qualified  service 
personnel. 

  If  the  overheat  symbol  appears  in  the  display  (    ) 

disconnect  the  instrument  from  the  mains  and  allow  to 
cool down. 

  This  unit  is  designed  to  give  minimum  “splash”  when 

connecting  to  an  earth  point  using  the  external  earth 
probe.    To  reduce  this  effect  further,  always  connect  the 
probe in a firm and positive manner. 

Summary of Contents for IPT 1800

Page 1: ...Instruction Manual IPT 1800 Digital LOOP PSC Tester FR EN IT DE ES P N P E...

Page 2: ...3 IV SPECIFICATIONS 4 4 1 Voltage Measurement 6 4 2 Manual and Autotest 6 4 3 Automatic Overheat Cut Out 6 V OPERATING INSTRUCTIONS 7 5 1 Correct Wiring 7 5 2 Measurement of the Loop Impedance 7 5 3 E...

Page 3: ...e to phase damage will result When conducting a test particularly on earth spikes do not touch any exposed metal work This is because the earth has a current flowing through it for the duration of the...

Page 4: ...easures low loop impedance resolution of 0 01 Ohm High impedance ranges permit direct measurements of ground spikes Automatic lock out if test resistor overheats Safe voltage measurement function Audi...

Page 5: ...EN 3 III INSTRUMENT LAYOUT P N P E AC CORD FI K EUR EATERNAL EARTH PROBE LCD DISPLAY...

Page 6: ...ction 240V 13A 6kA HRC ceramic fuses General Dimensions 180 L x 130 W x 70 H mm Weight Approx 800g include battery Test Current 25A approx 20Ohm Display Large style 3 1 2 digit custom LCD AC Test Peri...

Page 7: ...tegory 300V CAT single phase 230V Pollution Degree 2 This manual and product may use the following symbols adopted from International Safety Standards Equipment protected throughout by DOUBLE INSULATI...

Page 8: ...ual and Autotest Manual Press and release the Test Button The result will be displayed for 3s and then the display will revert to zero 4 3 Automatic Overheat Cut Out To test in accordance with the IEE...

Page 9: ...ON there is reversed phase and neon is ON there is reversed phase and neutral wiring 5 2 Measurement of the Loop Impedance Set the instrument to the 200 or 2000 range If the instrument is set to the 2...

Page 10: ...robe The phase earth loop impedance of exposed metal of bonding portable appliances or metal conduit etc can be tested using the external earth probe provided Connect the unit to the socket as normal...

Page 11: ...LCD with the appropriate units This will remain for 3s and then revert to zero An audible beep will sound on completion of the test For best results always test on the lowest possible range Note For l...

Page 12: ......

Reviews: