V808+ OPERATING INSTRUCTIONS
E
ng
lis
h
24VDC
3. Mount the gasket so that it will be sandwiched securely between the unit and the mounting panel.
Mounting Angle
The V8+ shall be installed within the angle of 15 to 135 degrees.
Electrical Wiring and Grounding
Electric shock hazard
Shut the power off before connecting the power supply cable.
Power Supply Cable Connection
Connect the power supply cable to the terminal
on the backside of the unit.
17.8
10.5
18.0
CN7
CN5
CF
LAN
U-B
U-A
RESET
CN1
MJ2
MJ1
When connecting the power supply cable, tighten the terminal screws to the following torque.
Screw Size
Tightening Torque
Crimp-style Terminal (Unit: mm)
M3.5
10.6 inch-lbf
(1.2 N·m)
The power source must be within the allowable voltage fluctuation (24 VDC
±
10%).
Use a power source with low noise between the cables or between the ground and the cable.
Use as thick a power supply cable as possible to minimize drop in voltage.
Keep power supply cables away from high-voltage, large-current carrying cables.
Be sure to attach the terminal cover to the terminal block.
Grounding
Be sure to establish a ground of AnyTouch.
(The level of grounding resistance should be less than 100
Ω
.)
An independent earth pole must be used for AnyTouch.
Use a cable which has a nominal cross section of more than 2 mm
2
for grounding.
Set the grounding point near AnyTouch to shorten the distance of grounding cables.
V8+ unit
Other
equipment
2. Insert four fixtures attached to the V8+ unit into the mounting holes, and tighten them with the locking screws.
(Tightening torque: 0.5 to 0.7 N·m)
* When the V8+ unit is attached to the mounting panel, the fixtures and frame grounds (FG) are connected.
To prevent static electricity, be sure to connect the mounting panel to the ground.
Fixtures
Mounting hole
V8 unit
Mounting panel
Mounting hole
Fixture dimensions
(Unit: mm)
Display
Display
Type: 24 VDC
Power supply
24 VDC
±
10%
Grounding
V8+ unit
Other
equipment
V8+ unit
Other
equipment
Independent grounding (best)
Grounding resistance:
less than 100
Ω
Grounding resistance:
less than 100
Ω
Shared grounding (good)
Cross grounding (prohibited)
7.1 or less
3.7
7.1 or less