Page 6 of 9
③.
When desired measurement unit is displayed, p
ress “MENU” and hold about 1second or the digit stops
blink to quit the setting mode.
Solution 2
①
. Move the flashing display to Zone
②
by pressing
“MENU”, then press “RESET” to choose measurement
unit.
②
. Press
“MENU” over 3 seconds to exit the setting mode.
(2) Resetting the accumulated total
Press
“MENU” for 10 seconds, the accumulated total will be reset to be “0”.
(3) Displaying current correction factor
Press “MENU” and “RESET” simultaneously and hold for 2 seconds. The display shows the correction factor.
4. CALIBRATION PROCEDURE
(1) Procedure for entering the correction factor directly
①.
Wait for the control valve to go to standby.
②.
Press the “MENU” key. Keep it pressed until the digit flashes in Zone
①
.
Press the “RESET” key to choose
the right digit from 0 to 9. Press the “MENU” key to go the next digit so that the Actual Value can be input.
③.
Make sure the correction factor is right and then press the “MENU” key. Keep it pressed until calibration is
finished and the factor is saved. The control valve will then return to standby.
(2) Modify the correction factor in field
①.
Press the “RESET” for 1 second, zone
①
displays
“0.00”.
②.
Start dispensing into a measuring glass.
③.
Stop dispensing when over 5 liters of volume is reached, then check the actual dispensed value. The
volume that is displayed on the LCD is the Display Value, not the Actual Value.
④.
Press the “MENU” key. Keep it pressed until the digit flashes in Zone
①
. Then press the RESET key to
choose the right digit from 0 to 9. Press the “MENU” key to go the next digit so that the Actual Value can be
input.
⑤.
Make sure the Actual Value is input correctly
and then press the “MENU” key. Keep it pressed until
calibration is finished and the factor is saved. The meter will then return to standby.
5 OPERATION
WARNING:
Follow the instructions in
PRESSURE RELIEF PROCEDURE before each operation.
WARNING:
➢
To ensure the proper amount of fluid is dispensed, always use the same measurement unit for a
particular fluid.
➢
Use a clean, calibrated container. If using a single container, clean it after each dispense.
➢
Always keep air pressure of pump at the lowest possible setting of the system for dispensing fluid.
➢
Ensure liquid enters the container from the bottom.
➢
Trigger the control valve gently.
①
. Grab the trigger (part# 1-4) gently, and then the control valve starts to work.
②
. Keep the trigger lock (part# 1-3) squeezed and depresses the trigger lock (part# 1-3) to keep the control
valve on.
③
. Disengage the trigger lock (part# 1-3) and release the trigger lock (part# 1-3) to stop dispensing.
6. BATTERY REPLACEMENT
If voltage is too low, low-power alarm device will be activated and light will flash in Zone
④
.
When the LCD
panel displays nothing or the light flashes in Zone
④
, the battery should be replaced. Follow the steps below to
replace new battery.
①.
Open the battery cover (part# 3-11) with a flat screwdriver.
②.
Remove the old battery. Discard the battery in accordance with local laws and ordinances.