PAX1 Motor Set Pressure Regulator 

User Manual

2

Section Page

Contents

1. Overview 

2

2. 

General Information 

3

3. Installation 

4

4. 

Electrical Connections, DC Power 

6

5. 

Electrical Connections, AC Power 

8

6. 

User Interface 

10

7. Commissioning 

11

8. 

Installation Dimensions 

13

9. Specifications 

20

10. Maintenance 

21

11. 

PAX1 Actuator & Pressure Regulator Assembly 

22

12. 

Notes  

23

1. 

Overview

The PAX1 Motor Set Pressure Regulator is a 
flexible linear actuator coupled to Fairchild 
precision pressure regulators and capable of 
controlling pressure ranges of 0-0.5 psig to 
0-3000 psig all housed in a flameproof enclosure. 
The unit is inherently lock in last place as the 
actuator will maintain its position upon loss of 
electrical power.

Power input options include 12-24 VDC or universal AC input 
95-250 VAC 47-63 Hz. 

The PAX1 can be actuated open loop using two optically 
isolated switch closure inputs (Up and Down) to change 
the pressure regulators setpoint. The PAX1 will continue to 
change the pressure regulator’s setpoint in response to the 
activated input until either of the adjustable range limits  
are reached.

The PAX1 has an isolated 4-20 mA control input to 
proportionally control the pressure regulator’s setpoint.  
In analog control mode, the unit is fail freeze upon loss of  
the control signal.

The actuator features UP and DOWN push buttons under  
the cover to facilitate commissioning and to permit local 
control of the pressure regulator’s setpoint. There is an 8 mm 
(

5

/

16

”) female hex motor drive interface under the cover 

to allow manual setpoint adjustment in the case of loss of 
electrical power. 

 

WARNING:

 

The cover must not be removed in 

the presence of a hazardous classified combustible 
atmosphere when power is present. Multiple power 
sources are possible including those operating the 
analog inputs, pulse inputs, alarm relays and feedback 
circuits.

The actuator includes two fully adjustable 1A, 250 VAC 
SPDT alarm relays (one High and one Low) providing alarm 
function when the pressure regulator output pressure 
reaches critical values. The relays are magnetically latched so 
the alarm switch states are maintained when the power is 
disconnected. This allows accurate alarm function on systems 
that remove power from the actuator between adjustments 
to conserve power as is typically done in solar powered 
installations.

The PAX1 offers an optional optically isolated electronic 
4-20 mA feedback output. This feedback feature is functional 
for both the pulse control and analog control configurations. 
The unit must be powered to facilitate the feedback output 
function.

The PAX1 can also be controlled via Modbus RTU digital 
communications over an optional optically isolated  
RS-485 network. The Modbus communications include a 
full featured command set allowing control, monitoring, 
commissioning and diagnostics capability over the digital 
communication. 

A4

US

US

A4

US

A4

US

A4

A4

US

 US

 A4

 US

 A4

A4

US

Summary of Contents for FAIRCHILD PAX1

Page 1: ...PAX1 Motor Set Pressure Regulator User Manual...

Page 2: ...sh buttons under the cover to facilitate commissioning and to permit local control of the pressure regulator s setpoint There is an 8 mm 5 16 female hex motor drive interface under the cover to allow...

Page 3: ...Ex tb IIIC T85 C T100 C Db II 2 GD T6 T85 C Ta 40 C to 65 C T5 T100 C Ta 40 C to 70 C IP66 IP68 FM Hazardous Area Conditions of use Hazardous locations wiring must comply with ANSI NFPA 70 NEC Wiring...

Page 4: ...eled on the regulator body under the ports Tighten connections securely NOTES Oil free air must be applied to the regulator Use a filter to remove dirt and entrained liquid in the air line ahead of th...

Page 5: ...rimp ferrules for wires entering the terminal block at connection 11 12 Crimp ferrule onto wire then clamp it in the terminal block Figure 1 Grounding An internal ground lug is provided Use the ring t...

Page 6: ...ol using an external loop supply DN UP RS 485 GND 1 2 3 4 5 6 7 8 9 10 11 12 SW2 Isolation Switch set to No FEEDBACK Switch set to PULSE Internal connection of NO ISOLATE switch Set to NO ANALOG CONTR...

Page 7: ...P SUPPLY External loop supply for Isolated Feedback Loop Figure 6 Power and Feedback Connections 1 2 3 4 5 6 7 8 9 10 11 12 RS 485 GND FEEDBACK PULSE CONTROL ANALOG CONTROL mA B A mA DC POWER RS 485 D...

Page 8: ...put control using an external loop supply 1 2 3 4 5 6 7 8 9 10 11 12 4 20 mA CONTROLLER Set switch to ANALOG DN UP RS 485 GND FEEDBACK PULSE CONTROL ANALOG CONTROL mA B A mA AC POWER RS 485 LOOP PWR S...

Page 9: ...9 NO NC C ALARM SW LO C NO NC NO NO NC NC ALARM SW HI Alarm Indicator Power Supply Figure 11 Alarm Switch Connections 4 Electrical Connections AC Power continued...

Page 10: ...eached thrust rod will move down only LIMIT LO Green Lo limit not reached thrust rod will move in both directions Red Lo Limit reached thrust rod will move up only ALARM HI Green Hi Alarm not reached...

Page 11: ...will ignore the previous pressure limits so that new limits may be set beyond the previously set limits The LIMIT LO and LIMIT HI LEDs will continue to operate from the previously set limits until ne...

Page 12: ...and DN RETRACT button and monitoring the Analog Feedback current on the milliammeter adjust the output current to the desired value 12 20 mA for this position 4 10 Press the SET button and wait for th...

Page 13: ...00 348 1 13 71 FRONT M5 GROUND SCREW HOLE HARDWARE INCLUDED 68 3 2 69 256 3 10 09 27 1 1 07 2 3 4 14 NPTF CONDUIT PORTS 38 1 1 50 76 3 3 00 19 1 0 75 BACK 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 1 4 18 NPT...

Page 14: ...T 78 0 3 07 TOP 175 9 6 93 152 4 6 00 FRONT M5 GROUND SCREW HOLE HARDWARE INCLUDED 133 4 5 25 27 1 1 07 275 3 10 84 86 7 3 41 38 1 1 50 BACK 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 14 18 NPTF OR 1 4 19 BSP...

Page 15: ...6 1 2 14 NPTF 1 2 14 BSPT 1 2 14 BSPP 3 4 14 NPTF 3 4 14 BSPT 3 4 14 BSPP INLET OUTLET 117 3 4 62 225 3 8 87 215 9 8 50 152 4 6 00 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST M5 GROUND SCREW HOLE HARDWARE INCL...

Page 16: ...1 16 27 NPTF OR 1 16 28 BSPT ORIENTATION WILL VARY 65 2 5 B B B B INLETS OUTLETS 333 13 1 55 70 55 78 3 1 154 6 1 19 0 8 A A INLET OUTLET 2 3 4 14 NPTF CONDUIT PORTS A A M5 GROUNDING SCREW HARDWARE I...

Page 17: ...BSPT CONDUIT PORTS 2 3 4 NPT GAGE PORT 1 4 18 NPTF OR 1 4 19 BSPT 31 1 2 19 8 38 1 5 260 10 2 37 1 5 INLET OUTLET 1 4 18 NPTF OR 1 4 19 BSPT 154 6 1 63 2 5 60 352 13 9 76 3 0 25 1 0 64 2 5 2 M8 X 1 2...

Page 18: ...REW HOLE HARDWARE INCLUDED OUTLET 1 8 NPTF OPTION U 1 8 BSPT GAGE PORT 1 8 NPTF OPTION U 1 8 BSPT 35 1 4 OUTLET 1 4 OR 3 8 NPTF OPTION U 1 4 OR 3 8 BSPT 258 10 2 INLET 1 4 OR 3 8 NPTF OPTION U 1 4 OR...

Page 19: ...T VACUUM PUMP 1 4 18 NPTF OR 1 4 19 BSPT 98 3 9 41 1 6 37 1 5 78 3 1 154 6 1 GAGE PORT 1 4 18 NPTF OR 1 4 19 BSPT 152 6 0 242 9 5 64 2 5 2 M8 X 1 25 MOUNTING HOLES 32 1 3 M5 GROUND SCREW HARDWARE INCL...

Page 20: ...4 VDC min limits 30 VDC max Alarm Switches 1 A 250 VAC SPDT Customer interface Electrical Connections Screw terminal block under cover 14 30 AWG Actuator speed Multi turn pot 1 2 60 mm min Limit adju...

Page 21: ...te Pulse mode and pressing the Jog DN button retract the thrust rod to its most retracted position Zero output pressure from the pressure regulator To expose the thrust rod remove the four bolts that...

Page 22: ...e Regulator Assembly Actuator Thrust Rod O Ring Thrust Rod Cap O Ring Pressure Regulator Mounting Bolts Pressure Regulator Mounting Plate Actuator Mounting Bolts O Ring Pressure Regulator Figure 20 PA...

Page 23: ...23 12 Notes...

Page 24: ...tork reserves the right to amend and change specifications without prior notice Published data may be subject to change For the very latest version release visit our website at www rotork com The name...

Reviews: