background image

CK

a

 & CK

ra

 

Atronik Start Up Guide

14

4. 

CK Atronik

4.1  Standard Settings

Configuration of the Atronik control module is performed via DIP switches located on the user interface PCB within the 
Atronik enclosure.

DIP switch functions

Label

Function

OFF

ON

ESD FUNCTION A

ESD Action

A OFF and B OFF = Disabled 
A ON and B OFF = Open

A ON and B ON = Stay put 
A OFF and B ON = Close

ESD FUNCTION B

ESD NC/NO

ESD Contact Form

ESD active when signal applied  
(normally open)

ESD active when signal removed  
(normally closed)

PTR LOCAL

Local Control

Local control is push-to-run

Local control is maintained

CLOSE DIRECTION

Direction

Clockwise to close

Anti-clockwise to close

PRIORITY A

2-Wire Priority

A OFF and B OFF = Close Priority 
A ON and B OFF = No Priority

A ON and B ON = Open Priority 
A OFF and B ON = No Priority

PRIORITY B

OPEN ACTION

Open Action

Stop on position limit

Stop on torque limit

CLOSE ACTION

Close Action

Stop on position limit

Stop on torque limit

LED

LED

Green = Close 
Red = Open

Red = Close 
Green = Open

STD/OPT CONTROL

Control Source

Hardwired control only

Option control only

POWER

Power

3-phase power supply

1-phase power supply

RELAY A

Relay Conditions

Relay settings are determined by a combination of A, B and C.  
Refer to below table for details.

RELAY B

RELAY C

SETUP

Actuator speed*

Actuator speed > 12 RPM

Actuator speed ≤ 12 RPM

*SETUP switch does not alter actuator output speed.

Standard Relay Conditions

RELAY A

RELAY B

RELAY C

Relay 1 Function

Relay 2 Function

OFF

OFF

OFF

Close Limit

Open Limit

OFF

OFF

ON

Torque Trip

Motor Stall

OFF

ON

OFF

Motor Stall

Thermostat Trip

OFF

ON

ON

Torque Trip Close

Torque Trip Open

ON

OFF

OFF

Mid Travel

Torque Trip

ON

OFF

ON

Remote Selected

ESD Active

ON

ON

OFF

Local Selected

Stop Selected

ON

ON

ON

Blinker

Hand Operation

A4

US

US

A4

US

A4

US

A4

A4

US

 US

 A4

 US

 A4

A4

US

Summary of Contents for CK Atronik Series

Page 1: ...CK Range CKa CKra Atronik Start Up Guide Modular Design Electric Valve Actuators...

Page 2: ...ver 1 000 service technicians are employed by our company partners and representatives providing the necessary worldwide infrastructure to fully support actuators in the field 1 CK Valve Actuation Wor...

Page 3: ...ar 11 Serial No Code Bar 12 QR Code 13 IP Degree 14 Address Atronik Name Plate Conduit Entries Switch Mechanism Cover Protective Earth Connection M6x1p x 10 Deep Plug and socket housing Atronik Interf...

Page 4: ...move the actuator to a mid travel position and confirm that none of the switches are active before beginning the test procedure 2 Test position switches in both directions using a flat screw driver to...

Page 5: ...river remains perpendicular to the switch mechanism faceplate when adjusting the torque trip limits to avoid introducing an offset to the set value 3 Commissioning C Open Torque Adjustment Point D Clo...

Page 6: ...ct direction This is done to avoid the need to wind through the whole mechanism to reach the limit position The correct direction to approach the limit is shown by the arrow next to the Adjustment Scr...

Page 7: ...rform two checks to confirm the OPEN limit position switch has been made correctly a The feel of the Adjustment Screw will noticeably change providing more mechanical resistance at the switching point...

Page 8: ...k on the Atronik status indicators during switch testing The main power supply must be maintained during this test procedure to ensure feedback via the Atronik It is not possible to test a switch that...

Page 9: ...orientation can be adjusted through 360 in 90 increments If this is a requirement then the following instructions must be adjusted by the same increment in the same direction 1 Move the actuator to th...

Page 10: ...Screw by 1 turn whilst holding the CLOSE portion of the Position Disc 8 Rotate only the red OPEN portion of the disc so that OPEN reads horizontally and then hold both portions in place 9 Tighten the...

Page 11: ...long the shaft against the spring to allow free rotation of the cam 3 Rotate the cam to ensure the desired switch behaviour is achieved The intermediate position switches can be supplied with normally...

Page 12: ...ntil the POT cannot rotate any further Confirm the POT is triggering the Close Limit indicator on the Atronik or reading the required resistance value 6 Refit the POT assembly to the AID chassis and e...

Page 13: ...the actuator to the Closed position limit using electrical operation or the handwheel 2 Connect a powered test meter across the CPT terminals and measure the transmitted current refer to actuator wir...

Page 14: ...B ON No Priority PRIORITY B OPEN ACTION Open Action Stop on position limit Stop on torque limit CLOSE ACTION Close Action Stop on position limit Stop on torque limit LED LED Green Close Red Open Red C...

Page 15: ...edback is transmitted via 4 20 mA to provide remote intermediate position indication Switch No Function OFF ON SW5 6 Positioner Inverse Control signal is Close low Open high Control signal is Close hi...

Page 16: ...isit our website at www rotork com The name Rotork is a registered trademark Rotork recognizes all registered trademarks Published and produced in the UK by Rotork POWJB0320 Rotork plc Brassmill Lane...

Reviews: