Atronik Start Up Guide
14
4.
CK Atronik
4.1 Standard Settings
Configuration of the Atronik control module is performed via DIP switches located on the user interface PCB within the
Atronik enclosure.
DIP switch functions
Label
Function
OFF
ON
ESD FUNCTION A
ESD Action
A OFF and B OFF = Disabled
A ON and B OFF = Open
A ON and B ON = Stay put
A OFF and B ON = Close
ESD FUNCTION B
ESD NC/NO
ESD Contact Form
ESD active when signal applied
(normally open)
ESD active when signal removed
(normally closed)
PTR LOCAL
Local Control
Local control is push-to-run
Local control is maintained
CLOSE DIRECTION
Direction
Clockwise to close
Anti-clockwise to close
PRIORITY A
2-Wire Priority
A OFF and B OFF = Close Priority
A ON and B OFF = No Priority
A ON and B ON = Open Priority
A OFF and B ON = No Priority
PRIORITY B
OPEN ACTION
Open Action
Stop on position limit
Stop on torque limit
CLOSE ACTION
Close Action
Stop on position limit
Stop on torque limit
LED
LED
Green = Close
Red = Open
Red = Close
Green = Open
STD/OPT CONTROL
Control Source
Hardwired control only
Option control only
POWER
Power
3-phase power supply
1-phase power supply
RELAY A
Relay Conditions
Relay settings are determined by a combination of A, B and C.
Refer to below table for details.
RELAY B
RELAY C
SETUP
Actuator speed*
Actuator speed > 12 RPM
Actuator speed ≤ 12 RPM
*SETUP switch does not alter actuator output speed.
Standard Relay Conditions
RELAY A
RELAY B
RELAY C
Relay 1 Function
Relay 2 Function
OFF
OFF
OFF
Close Limit
Open Limit
OFF
OFF
ON
Torque Trip
Motor Stall
OFF
ON
OFF
Motor Stall
Thermostat Trip
OFF
ON
ON
Torque Trip Close
Torque Trip Open
ON
OFF
OFF
Mid Travel
Torque Trip
ON
OFF
ON
Remote Selected
ESD Active
ON
ON
OFF
Local Selected
Stop Selected
ON
ON
ON
Blinker
Hand Operation
A4
US
US
A4
US
A4
US
A4
A4
US
US
A4
US
A4
A4
US