9
Setting Local Position Disc
The AID module includes a Local Position Disc that should be
configured to show Open and Close limit positions. A series
of reduction gears ensure a suitable range of travel can be
accommodated. If more turns are required please contact
Rotork.
CAUTION: The actuator position limits must be
configured prior to setting the Local Position Disc.
CAUTION: The AID cover orientation can be
adjusted through 360º in 90º increments. If this is a
requirement then the following instructions must
be adjusted by the same increment in the same
direction.
1) Move the actuator to the CLOSED limit using electrical
operation or the handwheel.
2) Loosen off the Position Disc Retaining Screw by 1 turn.
3) Rotate the Position Disc so that CLOSE reads horizontally
and hold the disc in place.
4) Tighten the Position Disc Retaining Screw until the Position
Disc is firmly locked in place.
5) Confirm the CLOSE label is aligned correctly with the cover
indication arrow.
3. Commissioning