Overview control elements ZEL RWA STZ 4503-T
Power
Power
230 VAC
230 VAC
Battery
Battery
Detector Line
Detector Line
Drive
Drive
Group
Group
Module
Module
Connector
Connector
X2
OFF
Service
X1
Service
X1
0
Reset
/
I
S1
8
1
ON
Display "system OK"
DIP switch
(see p. 27)
Display "mains"
Display "alarm"
Display "group fault"
Display "battery fault"
Display
"earthfault"
Display "line
fault"
Display "general fault"
Display
"not closed"
Vent
button CLOSE
Alarm button
Alarm reset button
Vent
button OPEN
Button "Line ON / OFF"
If the LED line fault flashes, the line is switched off,
e.g. for service reasons. You cannot activate the
control panel in this status.
In case of an actual line error the LED line fault is
permanently on.
Triggering an alarm is not possible during the
shutdown.
hold 3 s to
switch off
line / tip on
to switch on
= Display flashing
= Display ON
= Display OFF
Servicetimer is up
Line deactivated
Line fault
Display
"Line
fault"
Display
"OK"
Display
"General
fault"
Description
Line shutdown
Weather automatic
ZEL RWA STZ 4503-T
English
99.824.61 1.2/06/11
26/84
Only if wind detector or rain detector available.
Do not ventilate via smoke vent button, because
otherwise there would be a danger of damage
by wind or water.
optional automatic switch
Gap ventilation is not possible
no automatic switch
not
Upon triggering of the corresponding sensor, the
group of the control panel is closed.
If alarm is released by a smoke and heat vent
system, the system will open also in case of wind
and rain.
The weather automatic can be switched-off via an
, if gap ventilation is
required in case of bad weather.
in case of bad
weather, if
available.
If the weather automatic is switched on , the system
will automatically close in case of wind or rain. The
system will
automatically open again, if wind or
rain has stopped. Opening of the system for
ventilation via vent button.