Subject to change.
Roto Safe E601 – Eneo AF
IMO_66_EN_v2 / 104674
.
August 2019
.
1
Read the installation and operating instructions carefully.
Pass on the operating instructions to builders and end users.
1. Safety instructions
Installation and maintenance work may only be carried
out by specialised electrical companies. One is at the
risk of one’s life when working with 230 Volt (respectively
115 Volt) mains voltage. All work may only be carried out
when the power supply is switched off.
2. General description
The Roto Safe Eneo AF emergency exit lock is only to be
used in conjunction with Roto frame components and
HOPPE lever handle sets certified in accordance with DIN
EN 179.
Roto Safe Eneo AF locks mechanical-automatically when
closing over the door. Unlocking is carried out electroni-
cally, or manual operation is possible at any time. Roto
Safe Eneo AF can be used on emergency exit doors where
panic scenarios are not expected, as well as on apartment
entrance-doors and main entrance doors in single-family
houses and apartment buildings and is suitable for all door
materials (timber, PVC and aluminium). Even existing doors
can be retrofitted with the appropriate modification work on
the door.
3. Operation and function
Automatic locking
Both additional locking points on the Roto Safe Eneo AF
consist in each case of a latch and a bolt that is integrated
in the latch; the automatic bolt. When closing over the door,
the latches snap into its strikers, using the same principle
as on the latch in the main lock. In doing so, the bolts in the
latches are automatically activated and the door is securely
locked.
Unlocking the door from the outside
Depending on the admission control system installed,
unlocking can be triggered by means of a transponder, key
pad, magnetic card or manually via the cylinder.
Unlocking the door from the inside
The door can be opened at any time via the lever-handle. All
three latches and the two additional locking point’s auto-
matic bolts are withdrawn automatically.
4. Audible signals
1 x beep – Acknowledgement message:
Command
understood, procedure carried out correctly.
3 x short beep sound – Advisory message:
Command
understood, Roto Safe Eneo A cannot carry out the com-
mand, because the maximum number of cycles within the
prescribed time unit has been exceeded.
3 x dual tone beep – Error prompt:
The control unit
detected an overcurrent in the motor and has stopped as a
result.
4 x dual tone beep – Error prompt:
The connecting rod’s
final position was not reached within the maximum permis
-
sible time of 3 seconds.
5. Installation instructions
Upon installing the door, the functional clearance
(4–5 mm) is to be checked.
6. Application range
Roto Safe Eneo AF is designed for single leafed emergency
exit doors with lever-handles in accordance with DIN EN
179 where panic scenarios are not expected; e.g. offices etc.
Use only HOPPE lever-handle sets tested in accordance with
DIN EN 179 (DO 20.5.01, DO 20.5.02, DO 20.20.01,
DO 20.20.02, DO 20.7.01, DO 20.7.02).
7. Technical specifications
Power supply: 24 V DC (±5%), 2.5 A,
SELV output current in accordance with EN 60950-1
Continuous current absorption: 25 mA
Peak current absorption: 1,5 A (peak 2.3 A)
Relative humidity: ≤ 93 %
Outside temperature:
–25 up to +60°C (Transport –25 up to +70°C)
Standards: EN 60 730-1, EN 50090-2-2
Low voltage directives fulfilled, conforms to CE
Ro
to
S
af
e
E
6
01
–
E
ne
o
A
F
O
p
er
ati
n
g
i
n
str
uc
ti
o
n
s
EN
Fault
Cause
Rectification
System not
functioning
Eneo AF does not
react, no acoustic
signals
230 volt is not applied to the power supply
unit’s primary side.
Electrical installation work must - as specified in the
installation instructions - be carried out by qualified
personnel.
24 volt is not applied to the power supply unit’s
secondary side.
Check the clip contacts on the power supply unit.
24 volt is not applied to the Eneo AF.
Check the power supply line between the power
supply unit and Eneo AF and replace if need be.
24 volt is applied to the Eneo AF, however
+24 V /
GND are crossed.
Reverse the power supply’s polarity on the second-
ary side.
Still not functioning?
– Switch off the power supply, wait 10 seconds and
put it into operation again.
– Test with the Eneo Control Unit.
– Contact a specialist.
Eneo AF does not
lock automatically
The door is not completely closed.
Close the door completely, check the functional
clearance.
Door does
not unlock
No signal at the signal transmitter’s output
or no signal at Eneo AF’s input.
Check the settings and access control respectively.
Please refer to the access control’s operating
instructions!
Door or strikers not adjusted correctly (Overcur-
rent error prompt: Eneo AF beeps x 3).
Adjust the door or strikers (refer to point 5: installa-
tion instructions).