Your analyser’s commissioning test uses the test outlined in the UK’s TB143
but is not a substitute for an appliance manufacturer’s instructions.
Rotate dial to COM TEST position & follow your analyser’s instructions.
TEST 1 – check the appliance at max gas rate
Switch on appliance to max rate & zero your analyser in outside fresh air.
Once stable at its maximum gas flow rate; insert your flue probe into the
flue’s air inlet to measure CO2 levels – Readings must be stable & under or
equal to 0.20%.
TEST 2
Insert your flue probe into the appliance’s exhaust outlet to measure CO,
CO2 & RATIO levels – these must be within the manufacturer’s
instructions. If manufacturer’s instructions are not available CO must be
under 350ppm & RATIO under 0.0040.
TEST 3 – check the appliance at minimum gas flow rate where this is
possible
Once the appliance is stable at its minimum gas rate, measure CO, CO2 &
RATIO levels – these must be within the manufacturer’s instructions.
If manufacturer’s instructions are not available, CO must be under 350ppm
& RATIO under 0.0040.
TEST 4 – Measure Flow & Return Temperatures from the appliance
All measured readings are logged & can be printed to our optional KANE
IRP-2 printer or KANE’s App via wireless module.