background image

4 Installation

Installation manual

6

RRLQ011~016CA

Outdoor unit for air to water heat pump

4P385895-1A – 2016.03

c

a

b

d

2

Choose a piping route (a, b, c or d).

a

b

c

d

3

If you have chosen the downwards piping route:

▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.

c

c

b

a

4× Ø6 mm

4

Do the following:

▪ Connect the liquid pipe (a) to the liquid stop valve.
▪ Connect the gas pipe (b) to the gas stop valve.

a

b

5

Do the following:

▪ Insulate the liquid piping (a) and the gas piping (b).
▪ Make sure the piping and piping insulation do NOT touch the

compressor  (c),  the  compressor  terminal  cover  (d),  and  the
compressor bolts (e). If the liquid pipe insulation might touch
the  compressor  terminal  cover,  adjust  the  height  of  the
insulation  (f=no  insulation  around  the  compressor  terminal
cover (d)).

▪ Seal the insulation ends (sealant etc.) (g).

d

c

e

b
a

g

g

h

h

f

6

If  the  outdoor  unit  is  installed  above  the  indoor  unit,  cover  the
stop  valves  (h,  see  above)  with  sealing  material  to  prevent
condensed water on the stop valves from moving to the indoor
unit.

NOTICE

Any exposed piping might cause condensation.

7

Reattach the service cover and the piping intake plate.

8

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

a

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.2.2

To determine if oil traps are required

If oil flows back into the outdoor unit's compressor, this might cause
liquid compression or deterioration of oil return. Oil traps in the rising
gas piping can prevent this.

If

Then

The indoor unit is installed
higher than the outdoor
unit

Install an oil trap every 10 m (height
difference).

a

b

10 m

a

 Rising gas piping with oil trap

b

 Liquid piping

The outdoor unit is
installed higher than the
indoor unit

Oil traps are NOT required.

4.3

Checking the refrigerant piping

4.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

Summary of Contents for RRLQ011CAV3

Page 1: ...Installation manual Outdoor unit for air to water heat pump English Installation manual Outdoor unit for air to water heat pump RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 RRLQ011CAW1 RRLQ014CAW1 RRLQ016CAW1...

Page 2: ...D E HB HU HD B 200 A B C 200 200 200 B E 200 1000 500 A B C E 300 300 300 1000 500 D 500 D E 500 1000 500 B D 200 500 B D E HB HD HB HU 350 750 1000 500 HU HB HU 350 1000 1000 500 HB HU HB HD HD HU 20...

Page 3: ...pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17...

Page 4: ...rs Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the b...

Page 5: ...floor surface raise the unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes Model Bottom view mm RRLQ 35 36 61 99 16 71 60 159 154 182 a b c d 4 a Discharge sid...

Page 6: ...to the indoor unit NOTICE Any exposed piping might cause condensation 7 Reattach the service cover and the piping intake plate 8 Seal all gaps example a to prevent snow and small animals from entering...

Page 7: ...FORMATION Piping length is the one way length of liquid piping 4 4 2 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluo...

Page 8: ...m Ssc value RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 0 22 525 kVA RRLQ_W1 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produ...

Page 9: ...re b Bush c Nut d Frame e Hose 5 Reattach the service cover 6 Connect an earth leakage circuit breaker and fuse to the power supply line 4 5 4 To reposition the air thermistor on the outdoor unit Requ...

Page 10: ...tches 6 When operating do not short circuit protective device S1PH 7 Colours see below 8 Refer to the service manual for instructions on how to set the selector switches DS1 The factory setting of all...

Page 11: ...fin R10T RRLQ_V3 Thermistor fin RC RRLQ_V3 Signal receiver circuit S1NPH Pressure sensor S1PH High pressure switch TC RRLQ_V3 Signal transmission circuit V1R RRLQ_V3 Power module V1R V2R RRLQ_W1 Power...

Page 12: ...fen Tel 33 0 3 89 21 74 70 Fax 33 0 3 89 21 74 74 e ma il in fo rote x fr www ro tex fr DAIKIN AIRCONDITIONING BELGIUM NV A v e n u e F r a n k l i n 1 B B 1 3 0 0 W a v r e Tel 32 0 10 23 72 23 Fax 3...

Reviews: