4 Installation

Installation manual

5

RRLQ011~016CA
Outdoor unit for air to water heat pump
4P385895-1A – 2016.03

(mm)

>150

620

350

(345-355)

4× M12

a

a

Make sure not to cover the drain holes.

INFORMATION

The  recommended  height  of  the  upper  protruding  part  of
the bolts is 20 mm.

20

NOTICE

Fix the outdoor unit to the foundation bolts using nuts with
resin  washers  (a).  If  the  coating  on  the  fastening  area  is
stripped off, the nuts rust easily.

a

4.1.2

To install the outdoor unit

4× M12

4.1.3

To provide drainage

Make sure that condensation water can be evacuated properly.

NOTICE

If drain holes of the outdoor unit are covered by a mounting
base  or  by  floor  surface,  raise  the  unit  to  provide  a  free
space of more than 150 mm under the outdoor unit.

≥150 mm

Drain holes

Model

Bottom view (mm)

RRLQ

35

36

61

99

16

71

60

159

154

182

a

b

c

d (4×)

a

Discharge side

b

Drain holes

c

Knockout hole (piping intake - downwards route)

d

Anchor points

4.1.4

To prevent the outdoor unit from falling
over

1

Prepare  2  cables  as  indicated  in  the  following  illustration  (field
supply).

2

Place the 2 cables over the outdoor unit.

3

Insert  a  rubber  sheet  between  the  cables  and  the  outdoor  unit
to prevent the cable from scratching the paint (field supply).

4

Attach the cable’s ends. Tighten those ends.

4.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING

4.2.1

To connect the refrigerant piping to the
outdoor unit

1

Do the following:

▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).

Summary of Contents for RRLQ011CAV3

Page 1: ...Installation manual Outdoor unit for air to water heat pump English Installation manual Outdoor unit for air to water heat pump RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 RRLQ011CAW1 RRLQ014CAW1 RRLQ016CAW1...

Page 2: ...D E HB HU HD B 200 A B C 200 200 200 B E 200 1000 500 A B C E 300 300 300 1000 500 D 500 D E 500 1000 500 B D 200 500 B D E HB HD HB HU 350 750 1000 500 HU HB HU 350 1000 1000 500 HB HU HB HD HD HU 20...

Page 3: ...pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17...

Page 4: ...rs Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the b...

Page 5: ...floor surface raise the unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes Model Bottom view mm RRLQ 35 36 61 99 16 71 60 159 154 182 a b c d 4 a Discharge sid...

Page 6: ...to the indoor unit NOTICE Any exposed piping might cause condensation 7 Reattach the service cover and the piping intake plate 8 Seal all gaps example a to prevent snow and small animals from entering...

Page 7: ...FORMATION Piping length is the one way length of liquid piping 4 4 2 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluo...

Page 8: ...m Ssc value RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 0 22 525 kVA RRLQ_W1 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produ...

Page 9: ...re b Bush c Nut d Frame e Hose 5 Reattach the service cover 6 Connect an earth leakage circuit breaker and fuse to the power supply line 4 5 4 To reposition the air thermistor on the outdoor unit Requ...

Page 10: ...tches 6 When operating do not short circuit protective device S1PH 7 Colours see below 8 Refer to the service manual for instructions on how to set the selector switches DS1 The factory setting of all...

Page 11: ...fin R10T RRLQ_V3 Thermistor fin RC RRLQ_V3 Signal receiver circuit S1NPH Pressure sensor S1PH High pressure switch TC RRLQ_V3 Signal transmission circuit V1R RRLQ_V3 Power module V1R V2R RRLQ_W1 Power...

Page 12: ...fen Tel 33 0 3 89 21 74 70 Fax 33 0 3 89 21 74 74 e ma il in fo rote x fr www ro tex fr DAIKIN AIRCONDITIONING BELGIUM NV A v e n u e F r a n k l i n 1 B B 1 3 0 0 W a v r e Tel 32 0 10 23 72 23 Fax 3...

Reviews: