ROTEX Heating Systems GmbH
42
input
activated.
Other setting values do not apply.
d
Minimum rpm hot water
25
25
25
Settings reach 20 – 50% (40%=propane)
E
Min. leaving water temperature at OT
(OpenTherm) or RF thermostat
40
40
40
Settings reach 10 – 60°C
E.
Reaction OT and RF room thermostat
1
1
1
0= do not respond to hot water request if requested temperature
is lower than the set value par. E
1= respond to hot water request with minimum leaving water
temperature limited to set value par. E
2= respond to hot water request with maximum leaving water
temperature (on/off function)
F
Start rpm CH
70
70
70
Settings reach 50 – 99% of the set maximum rpm
(propane=50%)
F.
Start rpm hot water
70
70
70
Settings reach 50 – 99% of the set maximum rpm
(propane=50%)
h
Max. rpm fan (* 100 rpm)
45
46
46
Settings reach 40 – 50 (RKOMB22AAV1, RKOMB28AAV1 and
RKOMB33AAV1)
This parameter can be used to set the maximum rpm
n
Regulated temperature during boiler
operation (Ta)
80
80
80
Setting reach 60°C - 90°C
n.
Hot water temperature at Comfort/Eco
0
0
0
Setting reach: 0 or 40°C – 60°C
0= reheating temperature is equal to hot water temperature
O.
Wait time CH request response
0
0
0
Settings reach 0 – 15 minutes
o
Waiting time CH operation after hot water
operation
0
0
0
Settings reach 0 – 15 minutes
o.
Number of eco days
3
3
3
Settings reach 0 – 10
0 = Comfort function controllable by Open Therm room
thermostat
1 – 10 number of eco days
P
Anti-recycling time during CH operation
5
5
5
Minimum switch off time on CH operation
Can be set to 0 - 15 minutes
P.
Reference value hot water
24
30
36
0 = Flow switch applicable
24 = RKOMB22AAV1
30 = RKOMB28AAV1
36 = RKOMB33AAV1