Communications 

Prerequisites  

Before performing permanent modem installations, the 

modem that will be connected to the panel must be initialized 
from the computer running the VeriTrax software. 

AC-225 Hardware Installation and User Guide 

Page 39 

 

 

Computer Connections 

The MD-N33 must connect to the computer via a serial port. 

To connect to the PC: 

1.  Connect a 9VDC adapter to the first MD-N33. Make sure 

that the power LED (Red) is on. 

2.  Connect the PC, using an available COM port, to the MD-

N33 with cross serial cable

3.  Connect the MD-N33's RJ11 jack to the telephone line 

using the telephone cable. 

AC-225 Panel Connections 

1.  Connect a 9VDC adapter to the second MD-N33. Make 

sure that the power LED (Red) is on. 

2.  Connect the MD-N33's RJ11 jack to the telephone wall 

mount using the telephone cable.  

3.  Connect the MD-N33 DB9 female jack to the MD-14 DB9 

female jack. 

4.  Connect the AC-225 RS-485 outlet to the MD-14 4 wires 

cable. Make sure the J1 switch (on the AC-225) is set to RS-

485 Mode. 

 

 

Note: 

The telephone numbers shown in the examples below are 
for illustration purposes only. 
 

 

Note: 

Up to 32 panels can be connected on this RS-485 
network. 

Summary of Contents for AC-225 PCBA

Page 1: ...AC 225 Advanced Scalable Networked Access Controller Hardware Installation and User Guide July 2007 ...

Page 2: ......

Page 3: ...ply 13 3 5 Reader 15 3 6 MD IO84 15 4 Input and Output Requirements 16 4 1 Input Types 16 4 2 Inputs Description 22 4 3 Outputs 24 4 4 Card Readers and Keypads 25 5 AC 225 Hardware Settings 27 5 1 DIP Switch Configuration 28 5 2 Access Control Panel Baud Rate 28 5 3 Access Control Panel Type 29 5 4 Access Control Panel Addressing 30 6 Communications 33 6 1 Serial Network Connection 33 6 2 TCP IP N...

Page 4: ...system can control both single and double door entrances supports up to 30 000 users and uses flash memory to enable easy firmware upgrades For more information on the VeriTrax AS 225 system refer to the VeriTrax Access Control System User Guide The AC 225 consists of the following components AC 225 controller board Panel enclosure PS 14 power supply Power Transformer not included with the AC 225U...

Page 5: ...Introduction Figure 1 AC 225 panel AC 225 Hardware Installation and User Guide Page 4 ...

Page 6: ... every network 64 doors in every network 30 000 users 20 000 log events RS 232 or RS 485 serial communication up to 115200 bps 32 panels networked along one serial line RS 485 only On board TCP IP communication AC 225IP only Remote firmware upgrades Removable terminal blocks 1 2 VeriTrax AS 225 The VeriTrax AS 225 software system is custom designed to set up manage and supervise all aspects of an ...

Page 7: ...d flexibility in addition to a range of advanced control features Configurable Links The system s configurable links model makes it possible to trigger any chosen output automatically or report a configurable alarm based on a selected input This allows easy integration with other access systems such as intruder alarms CCTV systems and elevator controls VeriTrax AS 225 can also define a selected se...

Page 8: ...m 370mA General Inputs 4 supervised high impedance inputs 12 supervised inputs when used with the optional MD IO84 I O expansion board Maximum voltage 5V DC Relay Outputs 4 Relay outputs 8 outputs when used with the optional MD IO84 I O expansion board 5A Relay N O and N C options Reader Ports 2 Reader ports Output voltage 12V DC Max Current 300mA LED control output D0 D1 tamper input Visual Indic...

Page 9: ...00 bps 57600 bps 115200 bps Reader 2 reader ports Output voltage 12V Environmental Characteristics Operating Temperature Range 32 F 120 F 0 C 49 C Operating Humidity 0 90 Non condensing Dimensions Height x Width x Depth 10 4 x 13 2 x 3 4 inch 264 x 334 x 84 5 mm AC 225 8 38 lbs 3 80 Kg AC 225IP 8 40 lbs 3 81 Kg Weight AC 225U 5 95 lbs 2 70 Kg Transformer AC Transformer 120 220V AC 16V AC 2 5A 40VA...

Page 10: ...A From Transformer Backup Battery Charger 12VDC Lead Acid battery up to 7A H From Transformer Output Voltage 2 12V DC 0 5A Access control panel Output Voltage 3 12V DC 1 5A Power Supply Indication Tamper Output open collector Indicates faulty power Power LEDs Power In AC Green LED1 Main power Power Out DC Red LED2 Low voltage Charger BAT Red LED3 Backup battery low voltage ...

Page 11: ...for a network of AC 225 access control panels Veritrax Software Door 1 Door 3 Door 2 Door 4 Reader Keypad and Door Release Reader Reader Keypad and Door Release Exit Button Exit Button 2 Readers for Reader In and Reader Out AC 225 Single Door AC 225 Single Door AC 225 Double Door RS 485 232 Converter RS 232 RS 485 RS 485 RS 485 Up to 32 Access control panels AC 225 Single Door Figure 2 Sample AC 2...

Page 12: ...rvised Inputs 3 2 Inputs Wiring Supervised Inputs When wiring the AC 225 for supervised inputs resistors should be placed on the input switch and not on the terminal block For further details refer to Input and Output Requirements on page 16 AC 225 Hardware Installation and User Guide Page 11 ...

Page 13: ...strates wiring for two main types of 12VDC electrical release mechanisms Other electrical devices can be switched using the voltage free relay contacts Figure 4 Door Lock Failed Close Figure 5 Door Lock Failed Open AC 225 Hardware Installation and User Guide Page 12 ...

Page 14: ...iring between the PS 14 power supply and the AC 225 It is recommended to add a 12VDC lead acid backup battery if the main power supply fails If the main output is 12VDC wire it to the PS 14 Otherwise support your power supply according to the output requirements For further information refer to the Outputs section on page 24 ...

Page 15: ...AC 225 Panel Set Up Figure 6 Wiring Between PS 14 and AC 225 AC 225 Hardware Installation and User Guide Page 14 ...

Page 16: ...r Refer to the reader specifications for the maximum cable length typically 150m with an 18 AWG cable Figure 7 Reader Wiring 3 6 MD IO84 The MD IO84 is an optional I O expansion board which adds four relay outputs and eight supervised inputs to an Access Control Panel Attach the MD IO84 to the AC 225 s expansion slot For more information see the MD IO84 Installation and User Guide AC 225 Hardware ...

Page 17: ...2 resistors Inputs IN1 IN1A IN2 and IN2A may be configured individually as either supervised or non supervised inputs Configure each input separately via the VeriTrax AS 225 system Non supervised inputs have two states Normal State Abnormal State Supervised inputs have three states Normal State Abnormal State Trouble State The Trouble state is caused by either tampering with the input circuit or b...

Page 18: ...ection Normally Open Input has 2 states Switch Open Normal State Loop resistance Infinite open circuit Switch Closed Abnormal State Loop resistance 0 short circuit Figure 8 Normally Open Input Connection AC 225 Hardware Installation and User Guide Page 17 ...

Page 19: ...tion Normally Closed Input has two states Switch Closed Normal State Loop resistance 0 short circuit Switch Open Abnormal State Loop resistance Infinite open circuit Figure 9 Normally Closed Input Connection AC 225 Hardware Installation and User Guide Page 18 ...

Page 20: ...cts Normally Open Supervised Input has 3 states Switch Open Normal State Loop resistance 8 2K Switch Closed Abnormal State Loop resistance 0 short circuit Open circuit across input terminals Trouble State Loop resistance Infinite open circuit Figure 10 Normally Open Supervised Input Single Resistor AC 225 Hardware Installation and User Guide Page 19 ...

Page 21: ...o the input switch contacts Normally Open Supervised Input has 3 states 1 Switch Open Normal State Loop resistance 10 4K 2 Switch Closed Abnormal State Loop resistance 2 2K 3 Open circuit Infinite loop resistance or short circuit 0 resistance across input terminals Trouble State Figure 11 Normally Open Supervised Input Double Resistor AC 225 Hardware Installation and User Guide Page 20 ...

Page 22: ...t circuit across input terminals Trouble State Loop resistance 0 short circuit Figure 12 Normally Closed Supervised Input Single Resistor Normally Closed Supervised Double Resistor Input Connection Connect a 2 2K resistor in series to the input switch contacts Connect an 8 2K resistor parallel to the input switch contacts Normally Closed Supervised Input has 3 states Switch Closed Normal State Loo...

Page 23: ...Input Use the REX Input to open a door directly The following should be defined Single door controller Door 1 IN 1 Double door controller Door 1 IN 1 Door 2 IN 2 Typically the REX input is connected to a Normally Open push button that is located inside the premises The push button is generally located in an easy to access position and opens a door without reading a proximity card or PIN code AC 22...

Page 24: ... time Note Warning conditions are governed by the software set up See the VeriTrax Access Control System User Guide for more details After the access control panel enables access the lock is activated according to its programmed time until one of the following occurs The access control panel stops lock activation immediately after the door opens The access control panel waits for the door to close...

Page 25: ...the AC 225U the internal tamper switch must be connected to a UL Listed burglary unit Refer to the UL Listed burglary unit for connection instructions 4 3 Outputs Rosslare Security recommends the use of suppression diodes for all outputs that will be connected to inductive loads and activated by DC current such as Magnetic Lock Maglock or door strike devices Each suppression diode should be connec...

Page 26: ...ower to the door lock This restriction does not affect standard AC 225 models Note For UL installations the installer must configure the system as fail safe to comply with NFPA National Fire Protection Association regulations 4 4 Card Readers and Keypads Each access control panel can be connected to a maximum of two readers There are three available types of reader Card readers Keypads Combined ca...

Page 27: ...set the data transmission format for each reader The reader s tamper output connects to the access control panel s Reader Tamper input If the reader is interfered with an alarm can be generated The panel s Reader G LED output activates the reader s green LED input when operating in Card and PIN secure mode While this mode is in force users must enter a PIN on the keypad immediately after entering ...

Page 28: ...llers have two readers IN or OUT Outputs Door Lock output OUT 1 General purpose output OUT 1A General purpose output OUT 2 General purpose output OUT 2A Inputs Request to exit IN 1 Door monitor input IN 1A General purpose input IN 2 General purpose input IN 2A Access control panels configured as double door controller have two readers IN or OUT Outputs Lock output for Door 1 OUT 1 General purpose ...

Page 29: ...door controller or double door controller 4 5 6 7 8 The access control panel s VeriTrax network address Note Power down the access control panel before changing the DIP switch settings After changes have been made restart the panel The new settings are automatically defined after power up 5 2 Access Control Panel Baud Rate The Access control panel serial port baud rate set in dip switches one and ...

Page 30: ...ical to the host computer s serial port baud rate 5 3 Access Control Panel Type The Access control panel type is defined using the third DIP switch Set the panel to operate as either a single or double door controller The default access control panel setting is for a single door controller AC 225 Hardware Installation and User Guide Page 29 1 2 3 4 5 6 7 8 Figure 16 DIP Switch with Single Door Set...

Page 31: ...tput Requirements on page 16 Double Door Controller This access type has two readers IN and OUT as follows Outputs Door 1 lock strike General purpose output Door 2 lock strike General purpose output Inputs Release to exit door1 Door 1 monitor input Release to exit door 2 Door 2 monitor input 5 4 Access Control Panel Addressing The last 5 DIP switches are used to select the binary coded access cont...

Page 32: ...s available Address Switch 4 Switch 5 Switch 6 Switch 7 Switch 8 1 Off Off Off Off Off 2 Off Off Off Off On 3 Off Off Off On Off 4 Off Off Off On On 5 Off Off On Off Off 6 Off Off On Off On 7 Off Off On On Off 8 Off Off On On On 9 Off On Off Off Off 10 Off On Off Off On 11 Off On Off On Off 12 Off On Off On On 13 Off On On Off Off 14 Off On On Off On 15 Off On On On Off 16 Off On On On On 17 On Of...

Page 33: ... Off Off On 19 On Off Off On Off 20 On Off Off On On 21 On Off On Off Off 22 On Off On Off On 23 On Off On On Off 24 On Off On On On 25 On On Off Off Off 26 On On Off Off On 27 On On Off On Off 28 On On Off On On 29 On On On Off Off 30 On On On Off On 31 On On On On Off 32 On On On On On ...

Page 34: ...switch and the software are set to the same address There are three connection modes Serial Network RS 232 or RS 485 Modem Network TCP IP Network 6 1 Serial Network Connection The computer serial port controlling the access control panel is set from within the VeriTrax AS 225 software The default is 9600bps for direct connection to the computer When using an RS 232 connector only one access contro...

Page 35: ...position Up to 32 access control panel s can be linked together and connected to a single communication port on the computer Use the RS 485 interface for situations where there will be multiple controllers connected The serial port used to control the access control panel is assigned within the VeriTrax AS 225 software The Access control panel supports the two wire RS 485 interface RS 485 interfac...

Page 36: ... same way one after another AC 225 Hardware Installation and User Guide Page 35 AC 225 1 RS 485 AC 225 2 RS 485 AC 225 3 RS 485 L2 L1 L2 L1 L2 L1 Figure 18 Daisy Chaining At each end of the data line both where the panel connects to the computer and on the last panel in the network a termination resistor of 120Ω may be required Apply the resistor across the L1 and L2 connections These termination ...

Page 37: ...erating an MD N32 refer to the MD N32 User Manual LAN and WAN Requirements The devices can be connected to a TCP IP network using any valid network address Use a TCP IP connection when a LAN network already exists and the long RS 485 network is not required The following schematic illustrates the connection of a single AC 225 to a computer via a LAN network When the TCP IP connection is implemente...

Page 38: ...ess control panel network and the MD N32 converter RS 232 MD N32 TCP IP RS 232 Converter MD 14 RS 232 RS 485 Converter RS 485 RS 485 Access Control Panel 1 Access Control Panel 2 LAN WAN Figure 20 Connecting Multiple Access control panels with MD N32 The MD 14 is not required when using the AC 225IP AC 225IP RS 485 RS 485 Access Control Panel 1 Access Control Panel 2 LAN WAN Figure 21 Connecting M...

Page 39: ...uration with AC 225 RS 232 MD N33 Modem RS 232 Converter Telephone Line MD N33 Modem RS 232 Converter RS 232 RS 485 Access Control Panel MD 14 RS 232 RS 485 Converter Figure 22 Remote Site Modem Configuration Note For more information on modem connections refer to the MD N33 User Manual and the AS 225 software manual Hardware Requirements 2 Standard Telephone cables RJ11 plugs in both sides Crosse...

Page 40: ... COM port to the MD N33 with cross serial cable 3 Connect the MD N33 s RJ11 jack to the telephone line using the telephone cable AC 225 Panel Connections 1 Connect a 9VDC adapter to the second MD N33 Make sure that the power LED Red is on 2 Connect the MD N33 s RJ11 jack to the telephone wall mount using the telephone cable 3 Connect the MD N33 DB9 female jack to the MD 14 DB9 female jack 4 Connec...

Page 41: ...s warranty Unless otherwise requested by ROSSLARE ENTERPRISES LTD AND OR SUBSIDIARIES representative return of the failed product s is not immediately required If ROSSLARE has not contacted the Customer within a sixty 60 day holding period following the delivery of the warranty claim Customer will not be required to return the failed product s All returned Product s as may be requested at ROSSLARE...

Page 42: ...g with the Product if Product disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection and testing to verify any warranty claim ROSSLARE does not warrant the installation maintenance or service of the Product Service life of the product is dependent upon the care it receives and the conditions under which it has to operate In no event shall Rossla...

Page 43: ...m United States and Canada 1600 Hart Court Suite 103 Southlake TX USA 76092 Toll Free 1 866 632 1101 Local 1 817 305 0006 Fax 1 817 305 0069 E mail support na rosslaresecurity com Europe Global Technical Support Training Center HaMelecha 22 Rosh HaAyin Israel 48091 Tel 972 3 938 6838 Fax 972 3 938 6830 E mail support eu rosslaresecurity com South America Pringles 868 1640 Martinez Buenos Aires Arg...

Page 44: ......

Page 45: ...0706 0960202 00 www rosslaresecurity com ...

Reviews: