Reference Manual
00809-0100-4027, Rev AA
December 2005
4-9
Rosemount 4500
AMS
Right click on the device and select “Calibrate,” then “D/A Trim” from the
menu
.
1. Click
Next
after setting the control loop to manual.
2. Click
Next
after connecting the reference meter.
3. Click
Next
at the “Setting fld dev output to 4mA” screen.
4. Record the actual value from the reference meter, and enter it at the
“Enter meter value” screen and click
Next
.
5. Select
Yes
, if the reference meter value equals the transmitter output
value, or
No
if it does not. Click
Next
.
a. If Yes is selected, proceed to Step 6.
b. If No is selected, repeat Step 4.
6. Click
Next
at the “Setting fld dev output to 20mA” screen.
7. Repeat Step 4 - Step 5 until the reference meter equals the transmitter
output value.
8. Select
Next
to acknowledge the loop can be returned to automatic
control.
9. Select
Finish
to acknowledge the method is complete.
Digital-to-Analog Trim
Using Other Scale
The Scaled D/A Trim command matches the 4 and 20 mA points to a user
selectable reference scale other than 4 and 20 mA (for example, 1 to 5 volts if
measuring across a 250 ohm load, or 0 to 100 percent if measuring from a
Distributed Control System (DCS)). To perform a scaled D/A trim, connect an
accurate reference meter to the transmitter and trim the output signal to scale,
as outlined in the Output Trim procedure.
NOTE
Use a precision resistor for optimum accuracy. If you add a resistor to the
loop, ensure that the power supply is sufficient to power the transmitter to a
20 mA output with additional loop resistance.
AMS
Right click on the device and select “Calibrate,” then “Scaled D/A trim” from
the menu
.
1. Click
Next
after setting the control loop to manual.
2. Select
Change
to change scale, click
Next
.
3. Enter Set scale-Lo output value, click
Next
.
4. Enter Set scale-Hi output value, click
Next
.
5. Click
Next
to proceed with Trim.
6. Click
Next
after connecting the reference meter.
7. Click
Next
at the “Setting fld dev output to 4 mA” screen.
8. Record the actual value from the reference meter, and enter it at the
“Enter meter value” screen and click
Next
.
9. Select
Yes
, if the reference meter value equals the transmitter output
value, or
No
if it does not. Click
Next
.
Fast Keys
1, 2, 3, 2, 2