Quick Installation Guide
00825-0100-4051, Rev BA
June 2009
Rosemount 3051
9
S
TEP
4
CONTINUED
...
Signal Wiring Grounding
Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical
equipment. Grounding terminations are provided on the outside of the sensor module and
inside the Terminal Compartment. These grounds are used when transient protect terminal
blocks are installed or to fulfill local regulations. See Step 2 below for more information on
how the cable shield should be grounded.
1. Remove the Field Terminals housing cover.
2. Connect the wiring pair and ground as indicated in Figure 6. The cable shield should:
a.
Be trimmed close and insulated from touching the transmitter housing.
b.
Continuously connect to the termination point.
c.
Be connected to a good earth ground at the power supply end.
Figure 6. Wiring
3. Replace the housing cover. It is recommended that the cover be tightened until there is
no gap between the cover and the housing.
4. Plug and seal unused conduit connections.
PWR/
COMM
TEST
P/N
3151-9004-0001
AMBIENT
TEMPS
A
VOVE 60 REQUIRE
WIRING RA
TED
T
O
A
T
LEAST
90 C
DP
Trim shield and
insulate
Insulate
Shield
Connect Shield Back to the
Power Supply Ground
Ground for
Transient
Protection
Minimize
Distance
Minimize
Distance
4051 RevBA.fm Page 9 Monday, June 22, 2009 3:15 PM
Summary of Contents for 3051
Page 22: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 22 DOC ...
Page 23: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 23 ...
Page 24: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 24 ...
Page 25: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 25 ...
Page 26: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 26 NOTES ...
Page 27: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 27 NOTES ...
Page 28: ...Quick Installation Guide 00825 0100 4051 Rev BA June 2009 Rosemount 3051 28 ...