Page 8

RESM-4/RESM-5 Replacement

Wiring diagram of the RESM-4 (old)

U

I

RM

R

R

CURRENT TRANSFORMER

CO

N

TR

O

L

VO

LT

AGE

Suppress contactor

coil

HEATSEALING BAND

Or

from MAIN CONTROLLER RES

U

R

CONTACT

CONTACT           LOGIC SIGNAL

or

24VDC

0V

+signal

5

6

7

8

2

1

Twisted

LINE

13

NO

12

9

11

10

14

NC

15

C

ALARM OUTPUT

RELAY:   max. 100VDC
                         240VAC

                         1.5A 

ALARM  INPUT

(FROM MAIN CONTROLLER)

ALARM OUTPUT  RES

MAIN CONTROLLER

RESM-4

Relay

energized in

“go” state

0

+24V

In phase with

RES controller

Summary of Contents for RESISTRON RESM-4

Page 1: ... 4 and set the alarm threshold you do this on the RESM 5 with a display and four keys Older RESM 1 monitoring units for temperature controllers in the 2xx series cannot be converted using the RESM 5 Preparation 1 Select the unit Select an RESM 5 with the same line voltage as the old RESM 4 monitoring unit 115VAC 230VAC or 400VAC The RESM 5 monitoring unit has the following order numbers Line volta...

Page 2: ...un AUTOCAL Old setting ranges on the RESM 4 AUTORANGE function on the RESM 5 The RESM 5 monitoring unit has no coding switches on the housing The voltage 0 4 120V and current 30 500A ranges are automatically set when you run the AUTOCAL function Heed the information provided in the ROPEX Application Report in order to avoid malfunctions 4 The number of times the wire is laid through the PEX W2 3 o...

Page 3: ... higher level controller You should therefore only use this function if the risk analysis for the machine or plant allows To calibrate the zero point AUTOCAL on the RESM 5 Run the AUTOCAL function while the heatsealing band is cold Press the key repeatedly until menu step 107 is displayed Then select the AUTOCAL function by pressing the key If this function is executed correctly the main menu is a...

Page 4: ...u is not changed when you restore the factory settings As shipped condition The RESM 5 monitoring unit is shipped with the above factory settings and with the language set to German Menu Function Value 107 AUTOCAL temperature 20 C 204 Alloy 400ppm K 205 Range 300 C 206 Maximum temperature alarm threshold 40 C 213 Key lock No key 215 Alarm output Normal energized at alarm 225 Temperature unit Celsi...

Page 5: ...tion Power up message 208 Set point exceeded 206 Max temperature 210 Cooling mode 212 Relay K1 function 213 Key lock 207 Set point reached 205 Temperature range Setting Configuration 211 Heatslg time start Error 215 Alarm output 204 Temp coefficient 214 Cycles 107 Autocal 102 Preheat temp Autocal 5 6 209 Time control 1 2 216 Analog output 1 2 217 Temp diagnosis 218 Temp diag delay Continued on nex...

Page 6: ...lacement 221 Autocomp 220 Meas imp length 219 Heatup timeout Configuration 222 Output 1 Continued from previous page Back to home position 225 Temperature unit 226 System time 227 Visualization 228 Screensaver 229 RESET input ...

Page 7: ...rim U1 Twisted Auxilary power supply ANALOG OUTPUT actual value 0 10VDC 0V Internal ground NO EXTERNAL GROUNDIG ALLOWED Current transformer PEX W2 W3 11 10 IR NC NC NC NC 1 2 7 8 8 7 5 6 X Terminals on RESM 4 See RESM 5 documentation See RESM 5 documentation Note If error code 118 appears when you switch on the RESM 5 these cables should be reversed interchanged 9 10 11 or 12 13 14 or 15 Ground Mu...

Page 8: ... coil HEATSEALING BAND Or from MAIN CONTROLLER RES UR CONTACT CONTACT LOGIC SIGNAL or 24VDC 0V signal 5 6 7 8 2 1 Twisted LINE 13 NO 12 9 11 10 14 NC 15 C ALARM OUTPUT RELAY max 100VDC 240VAC 1 5A ALARM INPUT FROM MAIN CONTROLLER ALARM OUTPUT RES MAIN CONTROLLER RESM 4 Relay energized in go state 0 24V In phase with RES controller ...