Device functions
Page 30
RES-5007
Version 1
Part 1 of 3: Error messages (malfunctions)
NOTE:
The specified error messages are output as malfunctions (actual value output emits constant error
voltage; alarm LED is continuously lit; alarm relay is active).
Error
no.
Actual
value
output
Voltage
[V]
Cause
Measure if initial start-
up
Measure of machine in
operation, heating ele-
ment not changed
101
0.66
Current signal missing
Error range
Error range
102
1.33
Voltage signal missing
Error range
Error range
103
2.00
Voltage and current signals
missing
Error range
Error ranges
107
2.66
Temperature jump downward
Error ranges
(“Loose connection”)
Error ranges
(“Loose connection”)
108
Temperature jump upward
307
Temperature too low/high
(
chap. 8.9)
-
-
308
309
310
201
3.33
Network frequency missing/
fluctuates
Check network
Check network
202
Network frequency too large/
fluctuates
203
Network frequency too small/
fluctuates
304
4.00
Heat-up time too long
(
chap. 8.10)
Perform
RESET
Perform
RESET
901
4.66
Network voltage/synchronising
signal missing
Replace device
Replace device
913
Triac defective
Replace device
Replace device
914
Int. error, device defective
Replace device
Replace device
915
916
917
Slide switch for alarm output
incorrect
Check slide switch
Check slide switch
918