Float & Pump Replacement 

 PolarCool 

 

To

Pump

To Power

Plug

WHT

BLK

GRN

To

Pump

To Fan

Motor

To Power

Plug

Power Jumpers

RollSeal, Inc.  •  1733 County Road 68  •  Bremen, Alabama 35033  •  256-287-7000 

Units Manufactured Before May 26, 2015 

 

NOTE: If water is not disconnected, turn off the water hose.   

NOTE:  Do not allow the pump to run without water in the reservoir.  Without 

water, the pump may be damaged. 

 
INSTRUCTIONS 

1.  Disconnect all electrical power to PolarCool.  (i.e. Unplug power cord). 
2. Remove 

cooling 

pads. 

3.  Refer to Figure 3 at lower right.  Open electrical wiring box.

 

 

4.  For Single speed pump, refer to Figure 1 below.  For variable speed pump, refer to Figure 2 below.  Carefully 

disconnect pump wires only from terminals.  Pull wires through conduit and out of electrical box.  Unbundle pump 
power cord from other cords so that pump can be removed. 

5.

 

Disconnect water hose from pump.  Keep clamp for later use in Step 11. 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 Warning! 

Disconnect All Power Sources Before Installing This Equipment! Failure To  

Disconnect Power Source Can Result In Property Damage, Serious Injury Or Death! 

!

 