The XM-8DR is I/O expander with 8 NO/NC input lines and 8 relay outputs with single NO/NC 
contact each. The module is addressable and it is dedicated to devices with RACS Clock&Data 

interface, namely RACS 4 controllers. 
Optionally, XM-8DR can be used as standalone device (without communication with master device) 
and then its outputs are controlled by means of voltage signals at respective inputs. Currently the 

expander is available only as electronic module without enclosure and it is designated as XM-8DR-
BRD. With expander there are included adapters, which can be used for XM-8DR-BRD installation 

on DIN 35 mm rail. 
 

Table 1. Specification 

Parameter 

Description 

Supply voltage 

Nominal 12 VDC, min./max. 10-15VDC 

Current consumption 

25mA plus 40mA per each activated relay 

Relay max load 

30VDC/1.5A 

Input lines 

NO/NC inputs, electrically biased to +12V via 5.6k

Ω resistor, 

triggering level approx. 3 V 

Distance 

Between controller and XM-8DR-BRD expander: max. 150 m 

Environmental class 
(according to EN 50131-1) 

Class IV, -25C..+60C, relative humidity: 10 to 95% (no 
condensation), indoor conditions 

Dimensions (HxW) 

72x155 mm 

Weight 

115g 

Certificates 

CE 

 

2.

 

I

NSTALLATION

 

2.1 Terminals and connection diagram 

 

 

Fig. 1 XM-8DR-BRD I/O expander 

Summary of Contents for XM-8DR

Page 1: ...Roger Access Control System XM 8DR I O expander Operating Manual Firmware version 1 0 Hardware version 1 0 Document version Rev C...

Page 2: ...s designated as XM 8DR BRD With expander there are included adapters which can be used for XM 8DR BRD installation on DIN 35 mm rail Table 1 Specification Parameter Description Supply voltage Nominal...

Page 3: ...CS Clock Data bus Fig 2 Connection of XM 8DR BRD expander with PR402DR controller 2 2 LED indicators XM 8DR is equipped with ten LED indicators i e LED Link LED Power and 8 indicators associated with...

Page 4: ...D terminals of communicating devices must be connected by means of separate wire in order to equalize potentials Any wire section can be applied 2 4 Module mounting XM 8DR BRD module is not adapted to...

Page 5: ...d for ensuring compatibility with previous versions of XM 8 module and it is necessary to put jumper JP6 if XM 8DR is to operate with PRxx2 series controller RACS 4 JP7 pins can be used for selection...

Page 6: ...Page 6 of 8 Fig 4 XM 8DR module in elevator access control...

Page 7: ...XM 8DR to RUD 1 in accordance with table 5 Reset the device use RESET button or switch power supply off on Start RogerISP software and select communication port In Firmware window select firmware hex...

Page 8: ...ronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the...

Reviews: