Table 3. LED Power signalling 

State 

Description 

Steady light 

Normal operation 

Infrequently flashing light (2Hz) 

No communication 

Frequently flashing light (10Hz) 

Too low supply voltage 

Two short pulses every 2 seconds 

Microcontroller memory failure. In such case it is 

necessary to upload firmware or repair the expander. 

 

2.3 Power supply 

The XM-6DR requires 12VDC nominal power supply. If the voltage is below ~10V then the module 

stops its operation, deactivates all relays and signals the error by means of LED Power indicator 
(blinks 10 times per second). 

Note: For proper communication by means of RACS Clock& Data bus it is required to connect all 
GND terminals of devices. Such requirement is satisfied if both devices are supplied from the same 

point. If devices are supplied from different power supply units then GND terminals of 
communicating devices must be connected by means of separate wire in order to equalize 

potentials. Any wire section can be applied. 

2.4 Module mounting 

XM-6DR module is not adapted to outdoor operation and it is installer responsibility to apply proper 
method and location for module installation.  
 

 

Note: If any relay output of XM-6DR is used for switching 230VAC, then special 
precautions must be taken and all installation works must be performed by qualified 

and certified installer. 

 

 

Fig. 3 XM-6DR relay terminals 

Note: Single COM terminal is associated with two NO terminals (see fig. 3). Therefore it is 
necessary to ensure that sum of currents for particular pair of NO terminals does not exceed 10 A. 

 