background image

PS-15DR Installation Guide Rev.B.doc 

 

2013-04-23 

 

 

 

Strona 

5

 z 

7

 

All electrical connection should be carried out with AC supply off. The AC supply double coated 

cable should be fixed to 230VAC input terminals. 
Output voltage is available on two paralleled terminals AUX1 and AUX2 and supervised by common 

overcurrent and overvoltage protection. 

Note: PS-15DR will not start operation on reserve battery, the AC supply must exists in order to 
start device operation.  

7. S

AFETY PRECAUTIONS

 

The electric installation must be carried out by qualified person. For safety precautions make wiring 

so that the mains power supply switch and safety fuse are placed between PS-15DR and AC source 
and will be available for user (i.e. designate for that purpose a standalone automatic circuit breaker 

inside local distribution box). 

        

 

 

 

Fig.4 Access control application example 

 

Summary of Contents for PS-15DR

Page 1: ...Roger Access Control System Buffered Power Supply PS 15DR v1 0 Document version Rev B ...

Page 2: ...ule from unintentional penetration For device and user safety electronic circuit employs overvoltage overcurrent and thermal protection Device contains screw type terminal blocs and front panel with LED indicators PS 15DR enclosure is adapted for DIN 35mm T35 standard rail and should be powered directly from 230VAC 50Hz AC line 2 1 Output current PS 15DR maximal output current is ambient temperatu...

Page 3: ...se of battery reverse connection or output overload Note When battery is charged the max output current available on AUX terminals is reduced by value equal to actual battery charging current 4 PROTECTIONS PS 15DR has been equipped with following protections for user and device safety Main protection MP 230VAC input is protected with glass slow blow fuse that disconnects electronic module in case ...

Page 4: ...mm rail and in a vertical position as presented on Fig 3 Fig 3 General installation principle Power supply should be installed far enough from heat and moisture sources device ventilation holes shall not be obstructed and free air convection or forced air flow must be provided to ensure proper exploitation Without air circulation the power supply temperature can increase beyond permitted limits de...

Page 5: ...ltage protection Note PS 15DR will not start operation on reserve battery the AC supply must exists in order to start device operation 7 SAFETY PRECAUTIONS The electric installation must be carried out by qualified person For safety precautions make wiring so that the mains power supply switch and safety fuse are placed between PS 15DR and AC source and will be available for user i e designate for...

Page 6: ...re 5 C 40 C relative humidity 10 95 no condensation Output voltage 13 8VDC depending on battery charging phase may vary from 11 5V up to 13 8V level Max output current without battery 1 5A maximum output current is guaranteed for unlimited time for ambient temp range of 5 C to 30 C For temperatures between 30 C and 40 C output current must be externally limited according tradeoff characteristic fr...

Page 7: ...to the allotted locations for gathering used electrical and electronic devices Detailed information on recycling can be found at relevant local authorities in a disposing company or in a place where the product was bought Separate gathering and recycling of such wastes contributes to natural resources protection and is safe for humans health and for natural environment The equipment s weight is sh...

Reviews: