PS-15DR Installation Guide Rev.B.doc 2013-04-23
Strona
6
z
7
8. T
ERMINAL
D
ESCRIPTION
Terminal
Function
230VAC
230VAC line inputs, terminal N (NEUTRAL) and L (LINE)
BAT+
Battery positive terminal
BAT-
Battery negative terminal
AUX1+
Power supply AUX1 positive terminal
AUX1 -
Power supply AUX1 negative terminal
AUX2+
Power supply AUX2 positive terminal
AUX2 -
Power supply AUX2 negative terminal
9. T
ECHNICAL
D
ATA
Parameter
Value/Description
Supply voltage
Nominal 230VAC, permitted 195..265VAC, root mean square value (RMS)
Supply current
0.15A, root mean square value (RMS)
Supply line frequency
50Hz
Environmental class
(wg EN 50131-1)
Class I, indoor general conditions, temperature. +5°C - +40°C, relative humidity:
10..95% (no condensation)
Output voltage
13.8VDC, depending on battery charging phase, may vary from ~11.5V up to 13.8V
level
Max. output current
(without battery)
1.5A, maximum output current is guaranteed for unlimited time for ambient temp.
range of +5°C to +30°C. For temperatures b30°C and +40°C output
current must be externally limited according tradeoff characteristic from Fig.1.
During battery charging process output current will be reduced by value equal to
battery charge current
Max. battery output
current (momentary)
~2.5A
Initial battery charging
current
~0.3A
Battery cut off voltage
~10.0V, battery will be reconnected when AC supply returns
Battery type
12V sealed lead-acid battery (SLA or AGM)
Enclosure material
Polycarbonate plastic, UL94V0 flammability class
Dimensions W x S x G
85 x 62 x 73mm
Weight
~150 g
Certificate
CE