Device configuration 

The expander is configured within low level configuration by means of RogerVDM software. Such 
configuration must be done prior to connection to MC16 access controller particularly in regard of RS485 
address and reader parameters. The address of expander can also be programmed manually with jumpers 
on expander’s board. The address programmed with jumpers (hardware address) has higher priority than 
the address programmed with RogerVDM (software address). The factory new expander has ID=100 
software address. 

Addressing with jumpers 

Every time the address is modified, the expander must be restarted with RST button or switching power 
supply off and on. 
 

 

Fig. 7 

Manual addressing with jumpers on expander’s board 

Low level configuration with RogerVDM software 

 

Fig. 8 Connection of expander to RUD-1 interface 

  Connect the expander to RUD-1 interface as indicated in Fig.8.  

  Run RogerVDM program and select 

MCX v1.x

 device, firmware version, 

RS485

 communication 

channel and communication port (COM) emulated by RUD-1 interface. 

  Click 

Connect

 and program will display main configuration window with parameters read from the 

connected device. 

Summary of Contents for MCX402DR-BRD

Page 1: ...Roger Access Control System MCX402DR BRD I O expander Operating Manual Product version 1 0 Firmware version 1 0 2 255 Document version Rev B...

Page 2: ...ery The expander is offered individually as electronic module or as a component of MCX402 1 KIT for read in out door control or as a component of MCX402 2 KIT for two read in doors control In case of...

Page 3: ...from 230VAC 18VAC 40VA transformer and then it offers 13 8VDC power outputs AUX TML for external devices Optionally the expander can be supplied from 12VDC or 24VDC but in case of 12VDC the backup ba...

Page 4: ...mal state and is shorted to ground when triggered Output with reversed polarity operates with inverted logic It is shorted to ground in normal state and represents high impedance when triggered The co...

Page 5: ...ad in read out door with PRT readers A and Wiegand readers B Connection of expander to controller The expander is not operated as standalone device but as an extension of MC16 access controller It is...

Page 6: ...erVDM software address The factory new expander has ID 100 software address Addressing with jumpers Every time the address is modified the expander must be restarted with RST button or switching power...

Page 7: ...its every pressed key separately Range Yes No Default value Yes Min PIN length Parameter defines minimal number of digits in PIN Range 0 8 When set to 0 then PIN is disabled Default value 4 Max PIN le...

Page 8: ...ment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program CDI comment as above Card code length Parameter defines type of Wiegand 26 66bit interf...

Page 9: ...RT readers then another firmware must be uploaded Such firmware is available at www roger pl Firmware update is also used in case of migration from RACS 4 to RACS 5 when PR411 and PR402 controllers ar...

Page 10: ...ne CLK GND Ground DTA RACS CLK DTA interface line DTA IN3 IN3 input line GND Ground IN4 IN4 input line A RS485 communication bus line A TML Power supply output 12VDC 0 2A B RS485 communication bus lin...

Page 11: ...RD I O expander for door control with Wiegand or PRT readers MCX402 1 KIT 1 door expander kit MCX402 2 KIT 2 door expander kit Product history Version Date Description MCX402DR v1 0 10 2017 The first...

Reviews: