MCX402DR Operating Manual.doc
2018-09-03
6/11
Device configuration
The expander is configured within low level configuration by means of RogerVDM software. Such
configuration must be done prior to connection to MC16 access controller particularly in regard of RS485
address and reader parameters. The address of expander can also be programmed manually with jumpers
on expander’s board. The address programmed with jumpers (hardware address) has higher priority than
the address programmed with RogerVDM (software address). The factory new expander has ID=100
software address.
Addressing with jumpers
Every time the address is modified, the expander must be restarted with RST button or switching power
supply off and on.
Fig. 7
Manual addressing with jumpers on expander’s board
Low level configuration with RogerVDM software
Fig. 8 Connection of expander to RUD-1 interface
Connect the expander to RUD-1 interface as indicated in Fig.8.
Run RogerVDM program and select
MCX v1.x
device, firmware version,
RS485
communication
channel and communication port (COM) emulated by RUD-1 interface.
Click
Connect
and program will display main configuration window with parameters read from the
connected device.