MCX102-BRD Operating Manual
04.12.2020
8/12
Fig. 6 Connection to RUD-1 interface
Table 3. List of low level parameters
Communication settings
RS485 address
Parameter defines device address on RS485 bus. Range: 100-115.
Default value: 100.
RS485 communication timeout [s] Parameter defines delay after which device will signal lost
communication with controller. When set to 0 then signaling is
disabled. Range: 0-64s. Default value: 20s.
General settings
Single key press
When option is enabled then the whole PIN is transmitted to controller.
When option is disabled then every pressed key is transmitted
separately to controller. Range: Yes, No. Default value: Yes.
Min. PIN length
Parameter defines the minimal number of digits for PIN entered with
keypad. When set to 0 then PINs are disabled. Range: 0-8. Default
value: 4.
Max. PIN length
Parameter defines maximal number of digits in PIN. When set to 0
then PINs are disabled. Range: 0-8. Default value: 8.
[*] key clears PIN buffer
Parameter defines if already entered digits of PIN can be deleted with
[*] key. Range: Yes, No. Default value: Yes
Time between keys in PIN [s]
Parameter defines max. time between two consecutive key pressings.
Range: 1-64. Default value: 20.
PIN followed by [#] key
Parameter enables use of PINs with variable length. In such scenario
every PIN is concluded with [#] key. Range: Yes, No. Default value:
Yes.
Input types
IN1, IN2
Parameter defines input type. Range: [0]: NO, [1]: NC. Default value:
[0]: NO.
Input comments