background image

Digital Monitoring Products, Inc.

715 Loop Expander

715 LOOP EXPANDER

Description

The 715 Loop Expander allows you to increase the number of 12 VDC ungrounded loops available on DMP
command processor panels. The 715 provides an additional four Class B powered loops for connecting fire
alarm initiating and burglary type devices to the panel.

You can install the 715 on individual wire runs up to 500' from the panel using 22 gauge wire or up to 1000'
using 18 gauge wire.

Address Setting

The 715 Loop Expander uses two rotary switches labeled S1 and S2 to set the module's address. If you're
connecting the 715 to the panel's keypad data bus, use only the switch labeled S1.

To set the address, use a small slotted
screwdriver and gently turn the center arrow
on the switch clockwise to the number that
matches the keypad address. See Figure 2.

Each loop on the 715 Loop Expander can be
individually assigned to any active area in the
system.

Loop numbers restricted to device addresses: All loop numbers are preassigned to the device address
and cannot be changed. If device loops show open, verify the loops are correctly programmed.

Installation

3.3k 

 EOL Resistor

DMP Part # 309

alarm
circuit

alarm
circuit

alarm

circuit

alarm

circuit

3.3k 

 EOL

Resistor

DMP Part # 309

 Note: Connect the red wire to the

panel's smoke detector power.

SMOKE DETECTOR POWER

SERIAL DATA IN

AUX. OUTPUT

AUX. GROUND

BELL AND SMOKE GROUND

BELL OUTPUT 10.5-15 VDC

EARTH GROUND (14 AWG)

SERIAL DATA OUT

Command Processor
           Panel

Red

Yellow

Green

Black

Wire Harness

DMP Model WR-0012

Harness Color Code

To Panel

Loops

Red -      Positive 12 VDC
Yellow - Transmit Data
Green -  Receive Data
Black -   Ground

White/Brown -
White/Red -
White/Orange -
White/Yellow -

Loop 1
Loop 2
Loop 3
Loop 4

1

0

2 3 4

5

6

78

9

1

0

2 3 4

5

6

78

9

Figure 1: Panel and device connections to the 715 Loop Expander

0 1

2

3

4

5

6

7

8

9

0 1

2

3

4

5

6

7

8

9

S2

S1

Figure 2: Set switches to match device address

Example:

Rotary switches on the 715
set for keypad address two.

LT-0162 (7/95)

Digital Monitoring Products