MCX102-BRD Operating Manual
04.12.2020
11/12
Expander firmware update procedure:
1. Connect the device to RUD-1 interface (fig. 6) and connect the RUD-
1 to computer’s USB port.
2. Place jumper on FDM contacts
3. Restart device with RST button on device board or by switching supply off and on.
4. Start RogerISP software.
5. Select serial port emulated by RUD-1 interface and the option
USB-RS485 Converter
.
6. Select firmware file (*.hex), click
Program
and follow instructions on screen.
7. Once the firmware is uploaded remove the FDM jumper and restart the device.
8. Start Memory reset procedure.
6.
S
PECIFICATION
Table 4. Specification
Supply voltage
Nominal 12VDC, min./max. range 10-15VDC
Current
consumption
(average)
40mA (when relay off)
Inputs
Two (IN1, IN2) NO/NC inputs, triggering level app. 3.5V
Relay output
Single (REL1) relay output with isolated NO/NC contact, 30V/1.5A max load
Transistor output
Single (OUT1) transistor output, max load 15VDC/150mA
Distances
Up to 1200 m between controller and expander (RS485)
Up to 150m between expander and PRT or Wiegand terminals
IP Code
IP20
Environmental
class
(according
to
EN
50133-1)
Class I, indoor ge
neral conditions, temperature: +5°C to +40°C, relative
humidity: 10 to 95% (no condensation)
Dimensions W x S x G
80 x 54 x 20 mm
Weight
50g
Certificates
CE
7.
O
RDERING INFORMATION
Table 5. Ordering information
MCX102-BRD
Door expander; 2 inputs; 1 transistor output; 1 relay output; can operate with 2
PRTxx (Roger CLK/DTA ) or Wiegand 24..66 bit
ME-2-D
Metal enclosure; three DIN rails; 3.5A/13.8VDC monitored buffer power supply;
power distribution module; space for optional 12V/17Ah battery; tamper;
403x326x130mm
RUD-1
Portable USB-RS485 communication interface dedicated to ROGER access
control devices
8.
P
RODUCT HISTORY
Table 6. Product history
Version
Date
Description
MCX102-BRD v1.0
10/2017
The first commercial version of product