Expander firmware update procedure: 

1.  Connect the device to RUD-1 interface (fig. 6) and connect the RUD-

1 to computer’s USB port. 

2.  Place jumper on FDM contacts 
3.  Restart device with RST button on device board or by switching supply off and on. 
4.  Start RogerISP software.  
5.  Select serial port emulated by RUD-1 interface and the option 

USB-RS485 Converter

.  

6.  Select firmware file (*.hex), click 

Program

 and follow instructions on screen.  

7.  Once the firmware is uploaded remove the FDM jumper and restart the device.  
8.  Start Memory reset procedure.  

6.

 

S

PECIFICATION

 

Table 4. Specification 

Supply voltage 

Nominal 12VDC, min./max. range 10-15VDC 

Current 

consumption 

(average) 

40mA (when relay off) 

Inputs 

Two (IN1, IN2) NO/NC inputs, triggering level app. 3.5V 

Relay output 

Single (REL1) relay output with isolated NO/NC contact, 30V/1.5A max load 

Transistor output 

Single (OUT1) transistor output, max load 15VDC/150mA 

Distances 

Up to 1200 m between controller and expander (RS485) 

Up to 150m between expander and PRT or Wiegand terminals 

IP Code 

IP20 

Environmental 

class 

(according 

to 

EN 

50133-1) 

Class  I,  indoor  ge

neral  conditions,  temperature:  +5°C  to  +40°C,  relative 

humidity: 10 to 95% (no condensation) 

Dimensions W x S x G  

80 x 54 x 20 mm 

Weight 

50g 

Certificates 

CE 

 

7.

 

O

RDERING INFORMATION

 

Table 5. Ordering information 

MCX102-BRD 

Door  expander;  2  inputs;  1  transistor  output;  1  relay  output;  can  operate  with  2 
PRTxx (Roger CLK/DTA ) or Wiegand 24..66 bit 

ME-2-D 

Metal  enclosure;  three  DIN  rails;  3.5A/13.8VDC  monitored  buffer  power  supply; 
power  distribution  module;  space  for  optional  12V/17Ah  battery;  tamper; 
403x326x130mm 

RUD-1 

Portable  USB-RS485  communication  interface  dedicated  to  ROGER  access 
control devices 

 

8.

 

P

RODUCT HISTORY

 

Table 6. Product history 

Version 

Date 

Description 

MCX102-BRD v1.0 

10/2017 

The first commercial version of product 

 
 
 

Summary of Contents for MCX102-BRD

Page 1: ...Roger Access Control System MCX102 BRD Operating Manual Product version 1 0 Firmware version 1 0 4 or newer Document version Rev A...

Page 2: ...pology can be freely arranged as star tree or any combination of them except for loop The matching resistors terminators connected at the ends of transmitting lines are not required In most cases comm...

Page 3: ...tion RogerVDM Function are assigned to outputs within high level configuration VISO Multiple functions with different priorities can be assigned to the same output at the same time 2 INSTALLATION Each...

Page 4: ...plied from the same PSU then GND terminals of both devices must be connected with any wire 3 OPERATION SCENARIOS In typical scenario of operation MCX102 BRD expander is used to control single door by...

Page 5: ...ating Manual 04 12 2020 5 12 Fig 3 Scenario of operation with MCX102 BRD expanders Note The enclosure ME 2 D offers enough space and PSU to install up to three MCX102 BRD expanders in order to control...

Page 6: ...MCX102 BRD Operating Manual 04 12 2020 6 12 Fig 4 Typical door control with PRT series readers...

Page 7: ...RogerVDM program select MCX v1 x device firmware version RS485 communication channel and serial port with RUD 1 interface 3 Click Connect the program will establish connection and will automatically d...

Page 8: ...er Range Yes No Default value Yes Min PIN length Parameter defines the minimal number of digits for PIN entered with keypad When set to 0 then PINs are disabled Range 0 8 Default value 4 Max PIN lengt...

Page 9: ...I BUZZER LED SYSTEM LED OPEN LED STATUS comment Parameter defines any text or comment which corresponds to the object It is later displayed in VISO program Wiegand terminal 1 Terminal enabled When opt...

Page 10: ...restores factory default settings including ID 100 software address Expander memory reset procedure 1 Remove all connections from A B CLK and DTA terminals 2 Place jumper on 64 contacts and restart d...

Page 11: ...isolated NO NC contact 30V 1 5A max load Transistor output Single OUT1 transistor output max load 15VDC 150mA Distances Up to 1200 m between controller and expander RS485 Up to 150m between expander a...

Page 12: ...ectric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste con...

Reviews: